Fisher FIELDVUE DVC6200p Instruction Manual page 90

Digital valve controller
Hide thumbs Also See for FIELDVUE DVC6200p:
Table of Contents

Advertisement

Blocks— Transducer Block
June 2017
Table C‐3. Transducer Block Parameter Definitions
Label
PARAMETER_NAME
SELF_CALIB_STATUS
SERVO_GAIN_1
SERVO_RATE_1
SERVO_RESET_1
SETP_CUTOFF_DEC
SETP_CUTOFF_INC
Reserved by PI
TOTAL_VALVE_TRAVEL
TOT_VALVE_TRAVEL_LIM
TRAVEL_LIMIT_LOW
TRAVEL_LIMIT_UP
88
Index
RO /
Mode
Number
RW
0: Undetermined
1: Reserved
2: Aborted
3: Reserved
4: Error in mechanical
system (pressure
problem)
5-10: Reserved
12-127: Reserved
128: Self-calibration in
progress
129: Manual calibration in
progress
130: Quick Setup in
34
RO
progress (If initiated from
AUX terminals)
131: tuner active
132: tuner error (no
movement)
133: tuner error
(Accessories unstable)
134: tuner error (Other)
135: Self-calibration error
(Other)
136: Aborted from AUX
terminals
254: Successful
255: No valid data (bad
sensor reading)
35
RW
ALL
0 <= value <= 32768
36
RW
ALL
0 <= value <= 32768
0 <= value <= 32768,
37
RW
ALL
= 0 causes wind down
38
RW
OOS
-25% to 125%
39
RW
OOS
-25% to 125%
40-44
NA
45
RO
NA
46
RW
ALL
>=0%
AO.OUT_SCALE.EU_AT_
0%-10% to
47
RW
OSS
AO.OUT_SCALE.EU_AT_
100%+10%
AO.OUT_SCALE.EU_AT_
0%-10% to
49
RW
OOS
AO.OUT_SCALE.EU_AT_
100%+10%
Range
Default Value
0
4.4
3
9.4
0.50%
99.50%
1,000,000%
0%
100%
Instruction Manual
D103563X012
Protect
Description
Category
Data Type: Unsigned8
Result or status of the calibration
procedure. Initiating a new tuner or
calibration command will clear the
current bits.
N/A
Note: if the status is 'self-calibration
in progress' while power is cut off,
upon power being re-applied, this
parameter will show its last stored
value prior to the start of calibration.
Data Type: Float
SETUP
Proportional gain. Used for travel
control only.
Data Type: Float
SETUP
Derivative gain. Used for travel
control only.
Data Type: Float
Integral gain. Used for travel control
SETUP
only. If set to 0, will cause integrator
to wind down.
Data Type: Float
SETUP
Travel cutoff low
Data Type: Float
SETUP
Travel cutoff high
N/A
Data Type: Float
N/A
Accumulated travel in %.
Data Type: Float
Limit for TOTAL_VALVE_TRAVEL in
SETUP
%.
Data Type: Float
Lower limit of valve position in
SETUP
percent of travel span,
corresponding to OUT_SCALE.
Data Type: Float
Upper limit of valve position in
SETUP
percent of travel span,
corresponding to OUT_SCALE.