Instruction Manual
D103563X012
Table C‐6. Discrete Output Function Block Parameter Definitions
Label
PARAMETER_NAME
OUT_D
VALUE
STATUS
Reserved by PI
READBACK_D
VALUE
STATUS
Reserved by PI
Remote Cascade Input Discrete
RCAS_IN_D
VALUE
STATUS
Reserved by PI
IN_CHANNEL
INVERT
FSAFE_TIME
FSAFE_TYPE
FSAFE_VAL_D
Index
RO /
Mode
Number
RW
10
RW
MAN
0 = closed
1 = open
10.1
5,10,15... 255=%
10.2
11
12
RO
0 = closed
12.1
1 = open
5,10,15... =%
12.1
13
14
RW
ALL
0 = closed
1 = open
14.1
5,10,15... = %
14.2
15-16
Byte 1: TB_ID = 8
Byte 2: Relative index of
17
RW
ALL
the TB parameter
82 = TRAVEL_D
0: Not inverted
18
RW
ALL
1: Inverted
19
RW
ALL
>= 0
0: Value of
FSAFE_VAL_D is used as
setpoint, status of
OUT_D = UNCERTAIN -
Substitute Value
1: Use last valid
setpoint; status of
OUT_D = UNCERTAIN -
20
RW
ALL
Last usable Value or
BAD - No comm, no LUV
2: Actuator goes to
fail-safe position
defined by
ACTUATOR_ACTION ,
status of OUT_D = BAD -
non specific
0=closed
1=open
21
RW
ALL
5,10,15... 255=%
Range
Initial Value
0
0x80
0
0
0
0xC4
0x0852
0
0
1
0
Blocks— DO Function Block
Description
Data Type: 102
Process variable of the DO block in AUTO and RCAS
mode, and is the value specified by the
operator/engineer in MAN and LO. In case of BAD
status the valve goes to the position specified in
ACTUATOR_ACTION.
Data Type: Unsigned8
Data Type: Unsigned8
Indicates validity of VALUE.
Data Type: 102
Actual position of the device.
Data Type: Unsigned8
Data Type: Unsigned8
Indicates validity of VALUE.
Data Type: 102
Target setpoint and status provided by a supervisory
host in RCAS mode.
Data Type: Unsigned8
Data Type: Unsigned8
Indicates validity of VALUE.
Data Type: Unsigned16
Defines which transducer parameter provides input
to the DO READBACK_D parameter.
Data Type: Unsigned8
Indicates whether SP_D should be logically inverted
before writing to OUT_D in AUTO or RCAS mode.
Data Type: Float
Time in seconds from detection of failure of the
actual used setpoint (SP_D=BAD or RCAS_IN
_D<>GOOD) to the action of the block if the
condition still exists.
A comm timeout changes the status of the
transmitted setpoint to BAD.
Data Type: Unsigned8
Defines the reaction of the device if a failure of the
actual used setpoint is still detected after
FSAFE_TIME or if the status of actual used setpoint is
Initiate Fail Safe.
Data Type: Unsigned8
Setpoint used if FSAFE_TYPE = 0 and FSAFE is
activated
June 2017