Introduction and Specifications
June 2017
Table 1‐1. Specifications
Available Mounting
DVC6200p digital valve controller and DVC6215
feedback unit: J Integral mounting to Fisher
657/667 or GX actuators J Integral mounting to
Fisher rotary actuators, J Sliding‐stem linear
applications J Quarter‐turn rotary applications
DVC6205p base unit for 2 inch pipestand or wall
mounting (for remote-mount)
The DVC6200p digital valve controller or DVC6215
feedback unit can also be mounted on other
actuators that comply with IEC 60534-6-1, IEC
60534-6-2, VDI/VDE 3845 and NAMUR mounting
standards.
Function Block Suite
Standard (throttling) control includes AO, AI, DO, and
DI function blocks. Also included are a Logbook block
and an Alarm Transducer block.
Function Block Execution Times
AO Block: 6 ms
AI Block:
6 ms
DO Block: 6 ms
DI Block:
6 ms
Minimum Device Interval: 25 ms
Electrical Input
Voltage Level: 9 to 32 volts
Maximum Current: 19 mA
Reverse Polarity Protection: Unit is not polarity
sensitive
Termination: Bus must be properly terminated per
ISA SP50 guidelines
Digital Communication Protocol
PROFIBUS registered device
Certified to PROFIBUS Profile 3.02
(1)
Supply Pressure
Minimum Recommended: 0.3 bar (5 psig) higher
than maximum actuator requirements
Maximum: 10.0 bar (145 psig) or maximum pressure
rating of the actuator, whichever is lower
6
Supply Medium
Air or Natural Gas
Supply medium must be clean, dry and
non-corrosive.
Per ISA Standard 7.0.01
A maximum 40 micrometer particle size in the air
system is acceptable. Further filtration down to 5
micrometer particle size is recommended. Lubricant
content is not to exceed 1 ppm weight (w/w) or
volume (v/v) basis. Condensation in the air supply
should be minimized.
Per ISO 8573-1
Maximum particle density size: Class 7
Oil content: Class 3
Pressure Dew Point: Class 3 or at least 10_C less than
the lowest ambient temperature expected
Output Signal
Pneumatic signal, up to full supply pressure
Minimum Span: 0.4 bar (6 psig)
Maximum Span: 9.5 bar (140 psig)
Action: J Double, J Single Direct or J Reverse
Steady-State Air Consumption
Standard Relay
At 1.4 bar (20 psig) supply pressure:
Less than 0.38 normal m
At 5.5 bar (80 psig) supply pressure:
Less than 1.3 normal m
Low Bleed Relay
At 1.4 bar (20 psig) supply pressure:
Average value 0.056 normal m
At 5.5 bar (80 psig) supply pressure:
Average value 0.184 normal m
Maximum Output Capacity
At 1.4 bar (20 psig) supply pressure:
10.0 normal m
At 5.5 bar (80 psig) supply pressure:
29.5 normal m
Operating Ambient Temperature Limits
-40 to 85_C (-40 to 185_F)
-52 to 85_C (-62 to 185_F) for instruments utilizing
the Extreme Temperature option (fluorosilicone
elastomers)
-52 to 125_C (-62 to 257_F) for remote‐mount
feedback unit
-continued-
Instruction Manual
(2)(3)
3
/hr (14 scfh)
3
/hr (49 scfh)
3
/hr (2.1 scfh)
3
/hr (6.9 scfh)
(2)(3)
3
/hr (375 scfh)
3
/hr (1100 scfh)
D103563X012