Section 2 Wiring Practices; Quick Connect Cable Entry - Fisher FIELDVUE DVC6200p Instruction Manual

Digital valve controller
Hide thumbs Also See for FIELDVUE DVC6200p:
Table of Contents

Advertisement

Instruction Manual
D103563X012
Section 2 Wiring

Quick Connect Cable Entry

The DVC6200p is offered with a quick connect cable entry option, shown in figure 2‐1, for the PROFIBUS signal. The
quick connect cable entry provides an easier and more reliable interface to PROFIBUS devices and support modules by
providing a standard connection.
Figure 2‐1. Quick Connect Connector
1/2‐14 NPT
NOTE:
1. COLORS ARE WIRE COLORS.
GE61479-A
Note
The quick connect cable entry option is only available for intrinsically safe and non‐incendive installations.
Refer to figure 7‐2 for identification of parts.
WARNING
Personal injury or property damage, caused by fire or explosion, can result from the discharge of static electricity. Connect
2
a 14 AWG (2.08 mm
) ground strap between the digital valve controller and earth ground when flammable or hazardous
gases are present. Refer to national and local codes and standards for grounding requirements.
To avoid static discharge from the plastic cover, do not rub or clean the cover with solvents. Clean with a mild detergent
and water only.
To avoid personal injury or property damage, do not use the Quick Connect option on instruments in explosion‐proof or
flameproof installations.
1. The quick connect cable entry should be installed on the digital valve controller at the factory. If it is, proceed to
step 3. If not continue with step 2.
2. To install the Quick Connect:
a. Remove the terminal box cap (key 4) from the terminal box (key 3).
b. Apply sealant to the threads of the quick connector.
Practices2‐2‐
1 (BROWN)
2 (GREEN/YELLOW)
3 (BLUE)
4 (GREY)
Installation
June 2017
11