Table C‐10. Discrete Input Function Block Parameter Definitions
Label
PARAMETER_NAME
NUMBER_OF_PARAMETERS
ADDRESS_OF_VIEW_1
NUMBER_OF_VIEWS
Static Revision
ST_REV
Tag Description
TAG_DESC
Strategy
STRATEGY
Alert Key
ALERT_KEY
TARGET_MODE
Block Mode
MODE_BLK
ACTUAL
PERMITTED
NORMAL
Alarm Summary
ALARM_SUM
CURRENT
UNACKNOWLEDGED
UNREPORTED
DISABLED
BATCH
Reserved by PI
Index
RO /
Block
Number
RW
Mode
0.11
Octet 1 (MSB):
Slot
0.12
Octet 2 (LSB):
Index of View_1 parameter
for access
0.13
1
RO
0 to 65535
2
RW
ALL
3
RW
ALL
4
RW
ALL
0 to 255
Bit 7: OOS
5
RW
ALL
Bit 4: Man
Bit 3: Auto
6
RO
OOS+MAN+AUTO
6.1
6.2
6.3
Octet 1:
Bit 0: Discrete Alarm
Bits 1 - 6: Reserved
7
RO
Bit 7: Update Event - Set
after any STATIC
parameter is changed.
Octet 2: Reserved
7.1
7.2
7.3
7.4
8
9
Default
Range
Value
0x25
DI1: 0x0435
DI2: 0x0535
0x01
0
null
0
0
OOS
OOS
OOS+MAN+
AUTO
AUTO
0
0
0
0
Blocks —DI Function Block
Description
Data Type: Unsigned16
Number of used parameters in the block.
Data Type: Unsigned16
Address of View 1 parameter, see table C‐11.
Data Type: Unsigned8
Number of view objects of the block.
Data Type: Unsigned16
The revision level of the static data.
Increments by one each time a static
parameter changes, or a change of a table is
accepted. Reset to 0 in case of a cold start (ie if
FACTORY_RESET = 1 is set). Set to 1 if
overflow.
Data Type: Octet String
The user description of the intended
application of the block.
Data Type: Unsigned16
User-specified value used in configuration or
diagnostics as a key in sorting block
information.
Data Type: Unsigned8
The identification number of the plant unit.
This information may be used in the host for
sorting alarms or events generated by blocks.
Data Type: DS-37
Target mode of the block.
Data Type: DS‐69
Valid Bits: 7:OOS, 4:MAN, 3:AUTO
The actual, target, permitted, and normal
modes of the block.
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target
Data Type: DS‐42
Current alert status, unacknowledged states,
unreported states, and disabled states of the
alarms associated with the function block.
Data Type: Octet String
Current active alerts. Limit alarm bits are
cleared when the alarm condition is cleared.
Update event bit is cleared after 20s
(condensed status) or 10s (classic status).
Not used
Not used
Not used
Data Type: DS‐67
Not used
June 2017
121