D103563X012
Table C‐1. Physical Block Parameter Definitions
Label
PARAMETER_NAME
Block Mode
MODE_BLK
ACTUAL
PERMITTED
NORMAL
Alarm Summary
ALARM_SUM
CURRENT
UNACKNOWLEDGED
UNREPORTED
DISABLED
Software Revision
SOFTWARE_REV
Hardware Revision
HARDWARE_REV
Manufacturer Id
DEVICE_MAN_ID
DEVICE_ID
DEVICE_SER_NUM
Index
RO /
Mode
Number
RW
6
RO
7: OOS
6.2
3: Auto
7: OOS
6.3
3: Auto
7: OOS
6.4
3: Auto
7
RO
7.1
Octet 1
0 - 6: Reserved
7.2
7: Update Event - Set
after any STATIC
7.3
parameter is changed.
Octet 2: Reserved
7.4
8
RO
9
RO
10
RO
11
RO
12
RO
Initial
Valid Range
Value
Auto
OOS + Auto
Auto
0
0
0
0
Factory Set
0x13
Device ID
Null
Blocks— Physical Block
Description
Data Type: DS‐37
The actual, permitted, and normal modes.
Actual: The current mode of the block
Permitted: Allowed modes for TARGET_MODE
Normal: Desired operating mode
Data Type: DS‐42
Current alert status, unacknowledged states,
unreported states, and disabled states of the
alarms associated with the function block.
•Current active alerts cleared after 20s
(condensed status) or 10s (classic status)
•Unacknowledged, unreported, and disabled
not used.
Data Type: Visible string
Device's software revision
Data Type: Visible string
Device's hardware revision
Data Type: Unsigned16
Manufacturer identification number, used by an
interface device to locate the DD file for the
resource.
Data Type: Visible String
String containing the 16 character device ID
Of the form 0013DVCXXXXXXXXX, where
XXXXXXXXX = ELECTRONICS_SN
Data Type: Visible String
Serial number of the device. Set by factory.
June 2017