Fisher FIELDVUE DVC6200p Instruction Manual page 119

Digital valve controller
Hide thumbs Also See for FIELDVUE DVC6200p:
Table of Contents

Advertisement

Instruction Manual
D103563X012
Table C‐8. Analog Input Block Parameter Definitions
Label
PARAMETER_NAME
CHANNEL
PV_FTIME
FSAFE_TYPE
FSAFE_VALUE
Alarm Hysteresis
ALARM_HYS
High High Limit
HI_HI_LIM
Hi Limit
HI_LIM
Low Limit
LO_LIM
Low Low Limit
LO_LO_LIM
Index
RO /
Write Block
Number
RW
Mode
14
RW
ALL
16
RW
ALL
17
RW
ALL
18
RW
ALL
19
RW
ALL
21
RW
ALL
23
RW
ALL
25
RW
ALL
27
RW
ALL
Default
Range
Value
1: TB_ID = 8
2: Transducer Block
Parameter Relative
Index
56=FEEDBACK_VALUE
80=FINAL_POSITION_
VALUE
83=TRAVEL_TARGET
0x083A
84=SUPPLY_PRESSURE
85=PRESSURE_A
86=PRESSURE_B
87=PRESSURE_DIFF
95=TEMPERATURE
96=
TRAVEL_DEVIATION
97=DRIVE_SIGNAL
Positive
0
0: value FSAFE_VALUE
is used as OUT
1: use last stored valid
OUT value (if no valid
value is available, then
1
OUT value is initial
value in this case)
2: OUT has the wrong
calculated value and
status
0
0.5% of range
100
100
0
0
Blocks—AI Function Block
Description
Data Type: 101
Used to select the type of threshold that is used to
set the output.
Data Type: Float
Filter time of process variable
Contains the time constant for the rise time of the
Function Block output up to a value 63.21%
resulting from a jump on the input (PT1 filter).
Data Type: Unsigned8
Defines the reaction of the device, if a fault is
detected. The calculated ACTUAL_MODE remains
in AUTO.
If this parameter is not implemented, the AI
Function Block behaves like FSAFE_TYPE = 1
Data Type: Float
Default value for OUT parameter, if the status from
the primary value from the transducer block is bad.
Data Type: Float
Hysteresis. Prevents multiple triggering of the alarm
if the process variable is hovering around the
xx_LIM. Sensitivity is adjustable. Expressed as a
value below the high limit and above the low limit.
Data Type: Float
Value for upper limit of alarms. If the measured
variable is equal to or higher than the HI_HI_LIM
value the Limit Bit "high limited" in the Status Byte of
OUT and the HI_HI_Alarm bit in parameter
ALARM_SUM should be set to 1.
Data Type: Float
Value for upper limit of warnings. If the measured
variable is equal to or higher than the HI_LIM value
the Limit Bit "high limited" in the Status Byte of OUT
and the HI_Alarm bit in parameter ALARM_SUM
should be set to 1.
Data Type: Float
Value for lower limit of warnings. If the measured
variable is equal to or lower than the LO_LIM value
the Limit Bit "low limited" in the Status Byte of OUT
and the LO_Alarm bit in parameter ALARM_SUM
should be set to 1.
Data Type: Float
Value for lower limit of alarms. If the measured
variable is equal to or lower than the LO_LO_LIM
value the Limit Bit "low limited" in the Status Byte of
OUT and the LO_LO_Alarm bit in parameter
ALARM_SUM should be set to 1.
June 2017
117