Blocks— Transducer Block
June 2017
Table C‐3. Transducer Block Parameter Definitions
Label
PARAMETER_NAME
TAB_STATUS
POSITIONING_VALUE
VALUE
STATUS
90
Index
RO /
Mode
Number
RW
0: Not initialized
1: Good (new table is
valid)
2: Not monotonous
increasing (old table is
valid)
3: Reserved
4: Not enough values
transmitted (old table is
valid)
5: Too many values
transmitted (old table is
valid)
6 - 7: Reserved
8: Table is currently
loaded, set after
TAB_OP_CODE=1 and
before TAB_OP_CODE=3
(Additional access to
table not valid, old values
are valid)
9: Sorting and checking
of Table (Additional
access to table not valid,
56
RO
old values are valid)
10-19: Reserved
20: Not monotonous
increasing (table is not
initialized)
21: Reserved
22: Not enough values
transmitted (table is not
initialized)
23: Too many values
transmitted (table is not
initialized)
24 - 25: Reserved
26: Table is currently
loaded, set after
TAB_OP_CODE=1 and
before TAB_OP_CODE=3
(Additional access to
table not valid, table is
not initialized)
27: Sorting and checking
of Table (Additional
access to table not valid,
table is not initialized)
57
RO
57.1
-25% to 125%
57.2
Range
Default Value
0
0
0
Instruction Manual
D103563X012
Protect
Description
Category
Data Type: Unsigned8
Indicates the status of the
N/A
characterization table.
Data Type: 101
The actual command variable for the
device in units of OUT_SCALE, in
other words, setpoint in units of
N/A
OUT_SCALE, usually in percent.
Status BAD will drive the actuator to
the fail-safe position defined by
ACTUATOR_ACTION.
Data Type: Float
Physical target, or % of travel or
pressure range. Written by AO
channel 0x0839.
Data Type: Unsigned8
Indicates validity of VALUE, set by
out block OUT.STATUS..