Blocks— Transducer Block
June 2017
Table C‐3. Transducer Block Parameter Definitions
Label
PARAMETER_NAME
DI_LO_LO
VALUE
STATUS
DI_LO
VALUE
STATUS
DI_HI_HI
VALUE
STATUS
DI_HI
VALUE
STATUS
DEVICE_CALIB_PERSON
DEVICE_CALIB_LOC
PRESS_TUNE2
Pressure Integral Dead Zone
PRESS_INTEG_DEADZ
Pressure Integral Limit Hi
PRESS_INTEG_HI_LIM
Pressure Integral Limit LO
PRESS_INTEG_LO_LIM
Pressure Integral IC Hi
PRESS_INTEG_IC_HI
Pressure Integral IC Lo
PRESS_INTEG_IC_LO
Pressure MLFB Gain
PRESS_MLFB_GAIN
INST_ALERTS_CONFIG3
Temperature Hi Alert Point
TEMP_HI_ALRT_PT
Temperature Lo Alert Point
TEMP_LO_ALRT_PT
Supply Pressure Hi Alert Point
SUP_PRES_HI_ALRT_PT
Supply Pressure Lo Alert Point
SUP_PRES_LO_ALRT_PT
100
Index
RO /
Mode
Number
RW
122
N/A
1: Travel low low alert
active
122.1
RO
0: Otherwise
122.2
RO
123
N/A
1: Travel low alert active
123.1
RO
0: Otherwise
123.2
RO
124
N/A
1: Travel high high alert
124.1
RO
active
0: Otherwise
124.2
RO
125
N/A
1: Travel high alert active
125.1
RO
0: Otherwise
125.2
RO
126
RW
127
RW
128
> = 0%, < = 2.0%
128.1
RW
ALL
> = 0%, < = 100%
128.2
RW
ALL
< = 0%, > = -100%
128.3
RW
ALL
>= -100%, < = 100%
128.4
RW
ALL
>= -100%, < = 100%
128.5
RW
ALL
> 0, < = 100
128.6
RW
ALL
129
129.1
RW
ALL
> -76 F, < 257 F
129.2
RW
ALL
> -76 F, < 257 F
> = 0, < = 150
129.3
RW
ALL
> = 0, < = 150
129.4
RW
ALL
Range
Default Value
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
NULL
NULL
0.25%
50%
-50%
12%
-12%
35
186 F
-63 F
145 psig
15 psig
Instruction Manual
D103563X012
Protect
Description
Category
N/A
Data Type: Float
Data Type: Unsigned 8
1 if travel low low alert is active.
Controls DI channel 0x087A.
Data Type: Unsigned8
Indicates validity of VALUE.
N/A
Data Type: Float
Data Type: Unsigned 8
1 if travel low alert is active. Controls
DI channel 0x087B
Data Type: Unsigned8
Indicates validity of VALUE.
N/A
Data Type: Float
Data Type: Unsigned 8
1 if travel high high alert is active.
Controls DI channel 0x087C.
Data Type: Unsigned8
Indicates validity of VALUE.
N/A
Data Type: Float
Data Type: Unsigned 8
1 if travel high alert is active.
Controls DI channel 0x087D.
Data Type: Unsigned8
Indicates validity of VALUE.
Data Type: Octet String
CAL
Calibration person.
Data Type: Octet String
CAL
Calibration person.
Data Type: Float
SETUP
Integrator Deadzone, 1/2 width
Data Type: Float
SETUP
Integrator limits
Data Type: Float
SETUP
Integrator limits
Data Type: Float
SETUP
Integrator initial condition
Data Type: Float
SETUP
Integrator initial condition
SETUP
Data Type: Float
Data Type: Float
SETUP
Temperature HI Limits
Data Type: Float
SETUP
Temperature LO Limits
Data Type: Float
SETUP
Maximum supply pressure
Data Type: Float
SETUP
Minimum supply pressure

Advertisement