AC Power Circuit Breaker Requirements for the SRX5400 Services Gateway

Related
Documentation
114
NOTE:
In North America, AC power cords must not exceed 4.5 m
(approximately 14.75 ft) in length, to comply with National Electrical Code
(NEC) Sections 400-8 (NFPA 75, 5-2.2) and 210-52, and Canadian Electrical
Code (CEC) Section 4-010(3). The cords listed in
compliance.
Calculating Power Requirements for the SRX5400 Services Gateway on page 93
SRX5400 Services Gateway AC Power Supply Specifications on page 111
AC Power Circuit Breaker Requirements for the SRX5400 Services Gateway on page 114
Each AC power supply has a single AC appliance inlet located on the power supply that
requires a dedicated AC power feed. We recommend that you use a customer site circuit
breaker rated for 15 A (250 VAC) minimum for each AC power supply, or as required by
local code. Doing so enables you to operate the services gateway in any configuration
without upgrading the power infrastructure.
Calculating Power Requirements for the SRX5400 Services Gateway on page 93
SRX5400 Services Gateway AC Power Supply Specifications on page 111
AC Power Cord Specifications for the SRX5400 Services Gateway on page 112
Table 40 on page 112