Table 27: Sample Power Requirements For An Srx5400 Services Gateway - Juniper SRX5400 Hardware Manual

Hide thumbs Also See for SRX5400:
Table of Contents

Advertisement

SRX5400 Services Gateway Hardware Guide

Table 27: Sample Power Requirements for an SRX5400 Services Gateway

Chassis Component
Base system
Fan tray
MPC - slot 1/0
SPC - slots 1 and 2
SCB 0
Total power requirement
Total power requirement excluding cooling system
94
Calculate input power.
3.
Calculate thermal output (BTUs) for cooling requirements.
4.
The following sample configuration shows an SRX5400 Services Gateway chassis with
various power supplies and:
Two SRX5K-SPC-4-15-320 (SPC2) Services Processing Card (SPC) (slots 1 and 2)
One SRX5K-MPC (IOC2) with two MICs installed in it (slot 1/0)
One switch control board SRX5K-SCB (SCB1) or SRX5K-SCBE (SCB2) and one Routing
Engine SRX5K-RE-13-20 (RE1) or SRX5KRE-1800X4 (RE2) installed in it (SCB slot 0)
Calculate the power requirements (usage) as shown in
1.
Part Number
SRX5400-CHAS
SRX5400-FAN
IOC2
SRX-MIC-2X40-QSFP
SRX-QSFP-40G-SR4
SCP2
SCB1 with
RE1
Or
SCB2 with
RE2
Evaluate the power budget. In the case of a DC-powered chassis, evaluate the budget
2.
for each zone. In this step, we check the required power against the maximum output
power of available power supply options.
NOTE:
The power for the cooling system comes from a different tap on
the power supply, reserved for the cooling system only. The cooling system
power requirement does not need to be deducted from the output power
budget of the power supply.
Table 27 on page
94.
Power Requirement
40 W
75 W
570 W
585 W * 2 = 1170 W
150 W
90 W
>150 W
90 W
2095 W
2020 W
Copyright © 2017, Juniper Networks, Inc.

Advertisement

Table of Contents
loading

Table of Contents