AC Power Circuit Breaker Requirements for the SRX5800 Services Gateway

Related
Documentation
134
SRX5800 Services Gateway AC Power Supply Specifications on page 131
Calculating Power Requirements for the SRX5800 Services Gateway on page 107
AC Power Circuit Breaker Requirements for the SRX5800 Services Gateway on page 134
Each AC power supply has a single AC appliance inlet located in the chassis directly
above the power supply that requires a dedicated AC power feed. We recommend that
you use a dedicated customer site circuit breaker rated for 15 A (250 VAC) minimum for
each AC power supply, or as required by local code.
SRX5800 Services Gateway AC Power Supply Specifications on page 131
Calculating Power Requirements for the SRX5800 Services Gateway on page 107
AC Power Cord Specifications for the SRX5800 Services Gateway on page 132