SRX5400 Services Gateway Hardware Guide
Related
Documentation
Site Preparation Checklist for the SRX5400 Services Gateway
Table 26: Site Preparation Checklist
Item or Task
Verify that environmental factors such as
temperature and humidity do not exceed
services gateway tolerances.
Select the type of rack or cabinet.
92
Table 25: Services Gateway Environmental Specifications
Description
Altitude
Relative humidity
Temperature
Seismic
Maximum thermal output
NOTE:
Install the services gateway only in restricted areas, such as dedicated
equipment rooms and equipment closets, in accordance with Articles 110-16,
110-17, and 110-18 of the National Electrical Code, ANSI/NFPA 70.
SRX5400 Services Gateway Physical Specifications on page 90
SRX5400 Services Gateway Agency Approvals on page 365
SRX5400 Services Gateway Compliance Statements for EMC Requirements on page 366
The checklist in
Table 26 on page 92
preparing a site for services gateway installation.
For More Information ...
"SRX5400 Services Gateway Environmental
Specifications" on page 91
"SRX5400 Services Gateway Cabinet Size and
Clearance Requirements" on page
"SRX5400 Services Gateway Rack Size and Strength
Requirements" on page 99
Value
No performance degradation to 10,000 ft (3048 m)
Normal operation ensured in relative humidity range of 5% to 90%,
noncondensing
Normal operation ensured in temperature range of 32°F (0°C) to
104°F (40°C)
Nonoperating storage temperature in shipping container:
–40°F (–40°C) to 158°F (70°C)
Designed to meet Telcordia Technologies Zone 4 earthquake
requirements
AC power: 8065 BTU/hour (2365 W)
DC power: 7325 BTU/hour (2148 W)
summarizes the tasks you need to perform when
103,
Performed
By
Copyright © 2017, Juniper Networks, Inc.
Date