Parrdintr; Parrdptr - ABB ACSM1 Manual

Motion control system
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

394
Operation
Inputs
Outputs

PARRDINTR

(10101)
Illustration
Execution time
Operation
Inputs
Outputs

PARRDPTR

(10100)
Illustration
Execution time
Standard function blocks
Reads the scaled value of a parameter (specified by the Group and Index inputs). If the
parameter is a pointer parameter, the Output pin provides the number of the source
parameter instead of its value.
Error codes are indicated by the error output (Error) as follows:
Error code
Description
0
No error
<> 0
Error
See also blocks
PARRDINTR
Parameter group input (Group): DINT
Parameter index input (Index): DINT
Output (Output): DINT
Error output (Error): DINT
-
Reads the internal (non-scaled) value of a parameter (specified by the Group and Index
inputs). The value is provided by the Output pin.
Error codes are indicated by the error output (Error) as follows:
Error code
Description
0
No error or busy
<> 0
Error
Note: Using this block may cause incompatibility issues when upgrading the application
to another firmware version.
Parameter group (Group): DINT
Parameter index (Index): DINT
Output (Output): Boolean, INT, DINT, REAL, REAL24
Error output (Error): DINT
-
and PARRDPTR.

Hide quick links:

Advertisement

Table of Contents
loading