Code
Alarm
(fieldbus code)
2031
ENCODER 1 CABLE
(0x7389)
2032
ENCODER 2 CABLE
(0x738A)
2033
D2D COMMUNICATION
(0x7520)
Programmable fault:
COMM LOSS FUNC
2034
D2D BUFFER
OVERLOAD
(0x7520)
Programmable fault:
COMM LOSS FUNC
2035
PS COMM
(0x5480)
2036
RESTORE
(0x630D)
2037
CUR MEAS
CALIBRATION
(0x2280)
2038
AUTOPHASING
(0x3187)
2039
EARTH FAULT
(0x2330)
Programmable fault:
EARTH FAULT
Cause
Encoder 1 cable fault detected.
Encoder 2 cable fault detected.
On the master drive: The drive
has not been replied to by an
activated follower for five
57.02
consecutive polling cycles.
On a follower drive: The drive
has not received new reference
1 and/or 2 for five consecutive
reference handling cycles.
Transmission of drive-to-drive
references failed because of
message buffer overflow.
57.02
Communication errors detected
between the JCU Control Unit
and the power unit of the drive.
Restoration of backed-up
parameters failed.
Current measurement
calibration will occur at next
start.
Autophasing will occur at next
start.
Drive has detected load
unbalance typically due to earth
fault in motor or motor cable.
46.05
What to do
Check cable between FEN-xx interface and
encoder 1. After any modifications in cabling,
re-configure interface by switching drive
power off and on, or by activating parameter
90.10 ENC PAR
REFRESH.
Check cable between FEN-xx interface and
encoder 2. After any modifications in cabling,
re-configure interface by switching drive
power off and on, or by activating parameter
90.10 ENC PAR
REFRESH.
Check that all drives that are polled
(parameters
57.04
and 57.05) on the drive-to-
drive link are powered, properly connected to
the link, and have the correct node address.
Check the drive-to-drive link wiring.
Check the settings of parameters
57.07
on the master drive.
Check the drive-to-drive link wiring.
Contact your local ABB representative.
Check the connections between the JCU
Control Unit and the power unit.
If the JCU is powered from an external
supply, ensure that parameter
UNIT SUPPLY
is set to
(1) External
Contact your local ABB representative.
Informative alarm.
Informative alarm.
Check that there are no power factor
correction capacitors or surge absorbers in
motor cable.
Check that there is no earth fault in motor or
motor cables:
- measure insulation resistances of motor and
motor cable.
If no earth fault can be detected, contact your
local ABB representative.
311
57.06
and
95.01 CTRL
24V.
Fault tracing