45 MOT THERM PROT
Settings for thermal protection of the motor. See also section
protection
45
Firmware block:
MOT THERM PROT
(45)
Configures motor overtemperature
protection and temperature
measurement. Also shows the
estimated and measured motor
temperatures.
Block outputs located in other
parameter groups
45.01 MOT TEMP PROT
Selects how the drive reacts when motor overtemperature is detected.
(0) No
(1) Alarm
(2) Fault
45.02 MOT TEMP SOURCE
Selects the motor temperature protection. When overtemperature is detected the drive reacts as
defined by parameter
(0) ESTIMATED
Parameters and firmware blocks
on page 44.
1.17 MOTOR TEMP
1.18 MOTOR TEMP EST
FW block:
Inactive.
The drive generates alarm MOTOR TEMPERATURE when the
temperature exceeds the alarm level defined by parameter
MOT TEMP ALM LIM.
The drive generates alarm MOTOR TEMPERATURE or trips on fault
MOTOR OVERTEMP when the temperature exceeds the alarm/fault
level defined by parameter
TEMP FLT
FW block:
45.01 MOT TEMP
The temperature is supervised based on the motor thermal protection
model, which uses the motor thermal time constant (parameter
MOT THERM
45.06...45.08). User tuning is typically needed only if the ambient
temperature differs from the normal operating temperature specified
for the motor.
The motor temperature increases if it operates in the region above the
motor load curve. The motor temperature decreases if it operates in
the region below the motor load curve (if the motor is overheated).
MOT THERM PROT
(page 92)
(page 92)
MOT THERM PROT
45.03 MOT TEMP ALM LIM
LIM.
MOT THERM PROT
PROT.
TIME) and the motor load curve (parameters
WARNING! The model does not protect the motor if it does not
cool properly due to dust and dirt.
Thermal motor
(see above)
/
(see above)
45.03
45.04 MOT
45.10