10.01 EXT1 START FUNC
Selects the source for the start and stop control in external control location EXT1.
Note: This parameter cannot be changed while the drive is running.
(0) Not sel
(1) In1
(2) 3-wire
(3) FBA
(4) D2D
(5) IN1 F IN2R
(6) IN1S IN2DIR
2.18 D2D FOLLOWER CW
6.01 STATUS WORD 1
(page 105)
6.02 STATUS WORD 2
(page 106)
6.03 SPEED CTRL STAT
6.05 LIMIT WORD 1
(page 107)
6.07 TORQ LIM STATUS
6.09 POS CTRL STATUS
6.10 POS CTRL STATUS2
6.11 POS CORR STATUS
FW block:
DRIVE LOGIC
No source selected.
Source of the start and stop commands are selected by parameter
10.02 EXT1 START
IN1. The start/stop is controlled as follows:
Par. 10.02
Command
0 -> 1
Start
1 -> 0
Stop
Source of the start and stop commands are selected by parameters
10.02 EXT1 START IN1
and
controlled as follows:
Par.
10.02
Par.
10.03
0 -> 1
1
Any
1 -> 0
Any
0
Start and stop control from the source selected by parameter
CW
USED.
Start and stop control from another drive via D2D Control Word.
The source selected by
10.02 EXT1 START IN1
signal, the source selected by
start signal.
Par.
10.02
Par.
10.03
0
0
1
0
0
1
1
1
The source selected by
10.02 EXT1 START IN1
(0 = stop, 1 = start), the source selected by
the direction signal (0 = forward, 1 = reverse).
(page 100)
(page 107)
(page 108)
(page 109)
(page 110)
(page 111)
(see above)
10.03 EXT1 START
IN2. The start/stop is
Command
Start
Stop
Stop
is the forward start
10.03 EXT1 START IN2
Command
Stop
Start forward
Start reverse
Stop
is the start signal
10.03 EXT1 START IN2
Parameters and firmware blocks
121
10.13 FB
is the reverse
is