28.16 PI TUNE MODE
Activates the speed controller autotune function.
The autotune will automatically set parameters
TIME, as well as
ERR FTIME
is automatically set.
The status of the autotune routine is shown by parameter
WARNING! The motor will reach the torque and current limits during the autotune routine.
ENSURE THAT IT IS SAFE TO RUN THE MOTOR BEFORE PERFORMING THE
AUTOTUNE ROUTINE!
Notes:
• Before using the autotune function, the following parameters should be set:
• All parameters adjusted during the start-up as described in chapter
22.05 ZERO SPEED LIMIT
• Speed scaling and reference ramp settings in parameter group
26.06 SPD ERR FTIME
• If the User autotune mode is desired:
• The drive must be in local control mode and stopped before an autotune is requested.
• After requesting an autotune with this parameter, start the drive within 20 seconds.
• Wait until the autotune routine is completed (this parameter has reverted to the value
routine can be aborted by stopping the drive.
• Check the values of the parameters set by the autotune function.
See also section
(0) Done
(1) Smooth
(2) Middle
(3) Tight
(4) User
28.17 TUNE BANDWIDTH
Speed controller bandwidth for autotune procedure, User mode (see parameter
MODE).
A larger bandwidth results in more restricted speed controller settings.
0.00 ... 2000.00 Hz
28.18 TUNE DAMPING
Speed controller damping for autotune procedure, User mode (see parameter
MODE).
Higher damping results in safer and smoother operation.
0.0 ... 200.0
FW block: None
1.31 MECH TIME
CONST. If the User autotune mode is chosen, also
28.17 TUNE BANDWIDTH
Speed controller tuning
on page 51.
No tuning has been requested (normal operation). The parameter also
reverts to this value after an autotune is completed.
Request speed controller autotune with preset settings for smooth
operation.
Request speed controller autotune with preset settings for medium-
tight operation.
Request speed controller autotune with preset settings for tight
operation.
Request speed controller autotune with the settings defined by
parameters
FW block: None
Tune bandwidth for User autotune mode.
FW block: None
Speed controller damping for User autotune mode.
28.02 PROPORT GAIN
6.03 SPEED CTRL
25
28.17 TUNE BANDWIDTH
Parameters and firmware blocks
and
28.03 INTEGRATION
26.06 SPD
STAT.
Start-up
(page 15)
and
28.18 TUNE
DAMPING.
(0)
Done). The
and
28.18 TUNE
DAMPING.
28.16 PI TUNE
28.16 PI TUNE