Descriptions of System Data Fields
THE BLANK PROG RAMMING FORM SHOULD BE USED TO RECORD THE DATA FOR THIS INSTALLATION
Defaults (where applicable) Are Indicated In Text
The
following is a listing of all data fields in this control(presentedin numerical order). If
you have performed the pro gramming inshuctiona that were includedwith the instd.lation of
each of the various peripheral devices coveredin previous sections,this table will simply
serve as a referencefor all data fields in the system. If you have decidedto program all the
data fields in the system at one time (and therefore did not perform the programming
indicated previously in each section),you can use this listing to program all the data fields
*20
*21
*22
*23
*2.4
*25
INSTALLER
CODE
~
The
Installer codeis used to enter the 4-cligit Master security code
for each partition in the normal operation mode, via the keypad
connected to Partition 1. See "Master Code" in the
SYSTEM
OPERATION
sectionfor procedure.
Enter 4 digits, O-9. Default is 41-1-2.
QUICK ARM ENABLE
PartitionI
psrtition2
If enabled, the [#] key can be used instead of the securitycodewhen
~
the system.
Enter Ofor disabledor 1 for enabledfor eachpartition. Default is O.
RF SYSTEM
c1
This option is enabled (1) if a wirelessreceiveris used.
Enter 1 if 5881/5882 RF receiveris being used; enter Oif no receiver
is being used. Default is O (none).
FORCED
BYPASS FUNC1'iON
Partition1
Partition2
This f-ture
allowsall faulted zonesto be bypassedautomatically.
All zones that are bypassed by this function will be displayed after
the bypass is initiated. Enter, for eachpartition:
O= No forcedbypass.This is the dethlt.
1 = Allows automaticbypass of all open zones.
Enter WS for UL installations.
RF' HOUSE Ill CODE
m
The House ID identifiesreceiversand wirelesskeypads.
If a 5827 or 5827BD Wireless keypad is to be used, a House ID code
MUST be entered (01-31), and the keypad should be setto the same
ID. If no wirelesskeypad is to be usd
enter 00.
Partition 2 House ID = entered Partition 1 ID + 1 (use 01-30 for
partition 1 if wirelesskeypadsare used in both partitions).
WIRED
ZONE EXPANSION
Use this field to select the type of expansion unit being used, as
follows
O= none; 1 = 4219; 2 = 4229; 3 = 4204. Default is O.