ADEMCO Vista-20 Installation Instructions Manual page 92

Hide thumbs Also See for Vista-20:
Table of Contents

Advertisement

TO PROGRAM
SYSTEM STATUS
AND RESTORE
REPORT CODES
(*59 -76,
& *89)
The following is a set of guidelines to be used for progr amming report codes.
The actual digits that you enter depend upon the particular installation, and
should be in agreementwith you and the central station officereceiving the
signals. Use theseguidelinesto program this entire section.
With a 3+1 or 4+1 Standard Forraati Enter a codein the
first
box 1–9, ~
B, C, D, E,
or F. Enter "#+10 for A (this reports a "O" on some receivers),
"#+11" for B, "#+12"for C, "#+13 for D, "#+14"for E, "#+15" for F.
An entqy of "O in the
first
box wiIl disablea report.
An entry of "O"in the secondbox will result in automatic advance to the
next field when programming.
With an Expanded or 4+2 Formati
Enter codesin
both
boxes(lst and 2nd
digits) for 1–9, or A-F, as describedabove.
An entry of "O in the
first
box will disablea report.
An entry of "O"in the
second
box will eliminate the expanded messagefor
that report.
With Ademco Contact ID Reporting:
Enter a digit in the
first
box to
enable the zone to report. Use a different digit for each zone until you have
used up available digits. If the number of zones exceeds the number of
available digits, beginwith digit 1 again. This is an "enabling" codeonly and
is not the actual codesent to the cential station office. Entries in the second
boxeswill be ignored. For system status(non-alarm) codes,enter a "1" in the
first box for all the systemconditionsyou want to send to the centml station.
An entry of "O"inthe
first
box will disablethe report.
SYSTEM STATUS
*59
_
-OR
REpORT CODE (See ~x above.)
REPORT CODES
(*56456)
If the systemis armed and an Entry/Exit or Interior zone is still open
after the exit delay time has expired, an alarm will sound at the
keypad and external sounder (keypad also displays "Exit Alarm"). If
the system is disarmed before the end of the entry delay that
immediately follows, the alarm sounding will stop and no message
will be sent to the central station. The keypad will display CA
(fixed-wordkeypads)or CANCELLED MAR.M (Alpha keypads).
If the system is not
disarmed before the end of the entry delay
mentioned above, and an Entry/Exit or Interior zone is stiIl open, an
'exit alarmm message will be sent to the central station if an
Exit Error Report code is selected in this field.
The keypad will
display EA (fixed-word keypads) or EXIT ALARM (Alpha keypads),
and the alarm sounding will continueuntil the systemis disarmed (or
timeout occurs).
An "Exit Alarm" conditionwill alsoresult if a fault occursin an exit or
intenor zone within 2 minutes following the end of the exit delay, and
an "exitalarm" messagewill be sentto the central station.
If Contact ID format has been programmed, the messagewill contain
the zone number and error code374 (Troubl~Exit
Error) to define the
alarm as an Exit Error (rather than E/E or Interior). If 4+2 format is
used, the digit entered in this field will be sent followedby the second
digit of the programmed alarm codefor that zone. If 3+1 or 4+1 format
is used, only the digit entered in this field will be sent. This message
will go to the Primary Phone No. Under any of these conditions, no
Restoremessage will be sent.
If "O"is enteredin this field, no specialmessagewill be sent, only the
regular alarm and alarm restorecodefor the zone.
*60
TROUBLE
REPORT
CODE
(Seebox above)
m
*61
BYPASS REPORT
CODE
(Seebox above)
D
-92-