Terminal
Input /
symbol
output
Multifunction programmable analog
output. Default setting: output frequency.
The function can be changed to ammeter,
FM
Output
0-10Vdc voltage or 0-20mAdc (4-20mA)
current output by parameter 
setting.
Resolution Max. 1/1000.
Output
24Vdc power output
P24
This terminal can be used as a common
Input
terminal when an external power supply
is used by changing SW1 to PLC side.
DC power input terminal for operating the
control circuit. Connect a control power
Input
backup device (option) between +SU and
+SU
CC.
It is used with STO for safety function.
Output
+SU and STO terminals are short-
circuited by metal bar at default setting.
When +SU and STO are short-circuited,
the inverter is put into a standby state.
(Default setting) And when the circuit
between them is opened, the motor is
coasting stop. These terminals can be
STO
Input
used for inter lock.
This terminal is not a multifunction
Note 2)
programmable input terminal.
It is a terminal with the safety function
that complies with SIL II of the safety
standard IEC61508.
Note2) When STO terminal is used as the safety function, refer to section 9.3.
Function
1mAdc full-scale
ammeter or
QS60T(option)
0-20mA (4-20mA)
DC ammeter
Permissible load
resistance:
750Ω or less
0-10V DC volt
meter
Permissible load
resistance:
1kΩ or more
24Vdc-100mA
-
Voltage: 24Vdc±
10%
Current: 1A or
more
-
Independently of
SW1
ON: DC17V or
more
OFF: Less than
DC12V
(OFF: Coast stop)
B-9
Electrical
Inverter internal circuits
specifications
+24V
FM
P24
SW1
+SU
27.4k
STO
E6581697
121
+
+24V
Voltage
Current
+
68
2
EXT
+24V
Current
limiter
U
+5V
CPU
10k