Toshiba TOSVERT VF-MB1 Instruction Manual page 236

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-MB1:
Table of Contents

Advertisement

Ex.) When using the S3 terminal as the tracing back trigger signal terminal
Title
f116 Input terminal function selection 6 (S3)
Setting value 77 is reverse signal.
Note 1: If the inverter trips when no trigger signal is given, trace data is overwritten with tripping data.
Note 2: Trace data is overwritten each time a trigger signal is given.
Note 3: When retry operation is occurred, the data at first tripping is written. The trace data is cleared at retry success.
[Setup values of f742 to f745 ]
Default setting
0
1
2
3
4
5
6
6
7
9
10
11
12
13
14
18
20
21
23
24
25
26
27
40
41
42
Acquisition of trace data
Trace data is acquired through a communication device.
Function
Communication
No.
FD00
Operation frequency
FD03
Output current
FD02
Frequency setting value
FD04
Input voltage (DC detection)
FD05
Output voltage (command value)
FD29
Input power
FD30
Output power
FD18
Torque
FD23
Motor cumulative load factor
FD24
Inverter cumulative load factor
FD25
PBR (Braking resistor) cumulative load factor
FD15
Frequency setting value (after compensation)
FE35
VIA input value
FE36
VIB input value
FA51
Arbitrary code from communication
FE37
VIC input value
FE56
Pulse train input value
FD22
PID feedback value
FE76
Input power
FE77
Output power
FE26
Motor load factor
FE27
Drive load factor
FD06
Input terminal status
FD07
Output terminal status
FD01
Inverter status
F-116
Adjustment range
0-203
Trace (monitor) function
E6581697
Example of setting
76: TRACE (Trace
back trigger signal)
Communication
unit at tracing
0.01Hz
0.01%
0.01Hz
0.01%
0.01%
0.01kW
0.01kW
0.01%
0.01%
0.01%
0.01%
0.01Hz
0.01%
0.01%
-
0.01%
1pps
0.01Hz
1kWh
1kWh
1%
1%
-
-
-