6.30 Tracing functions

f740 : Trace selection
f741 : Trace cycle
 Function
These parameters are used to memorize and read out the data collected at the time of tripping or triggering.
Up to 4 kinds of data can be selected from 43 kinds of data, and the data collected at 100 consecutive
points can be stored in memory as trace data.
Here is the time at which trace data is acquired.
 Tripping: Data collected before the occurrence
 Triggering: Data collected after triggering
Note: To read data on a PC.
6
Title
f740
f741 Trace cycle
f742 Trace data 1
f743 Trace data 2
f744 Trace data 3
f745 Trace data 4
Note1: For saving trace data, do not disconnect power supply after inverter tripped.
Note2: When f741=0 or 1 setting, set the value of f678 (Constant at the time of filtering) lower than
f741 setting time (trace cycle time).
Function
Trace selection
f742 : Trace data 1
f743 : Trace data 2
f744 : Trace data 3
f745 : Trace data 4
Adjustment range
0: Disabled
1: At tripping
2: At triggering
3: 1+2
0: 4ms
1: 20ms
2: 100ms
3: 1s
4: 10s
0-42
0-42
0-42
0-42
F-114
E6581697
Default setting
1
2
0
1
2
3