Parameter setting

Title
Frequency setting mode selection 1
fmod
f207 Frequency setting mode selection 2
f200 Frequency priority selection
1) External switching (Input terminal function 104/105 : FCHG)
Frequency priority selection parameter f200 = 0
Switching between the command specified with fmod and f207 can be made by entering a command
from a terminal board.
To do so, however, the frequency command forced switching function (input terminal function selection: 104)
needs to be set beforehand to an input terminal board.
If an OFF command is entered to the input terminal board: The command specified with fmod will be
selected.
If an ON command is entered to the input terminal board: The command specified with f207 will be
selected.
Note) Input terminal function 105 is inverse.
2) Automatic switching by frequency command
Frequency priority selection parameter f200 = 1
The switching between the command specified with fmod and f207 is done automatically according to
the frequency command entered.
If the frequency set with fmod is above 1Hz: The command specified with fmod will be selected.
If the frequency set with fmod is 1Hz or less: The command specified with f207 will be selected.
Refer to the figure of "Example of run and frequency command switching" in section 5.6
Function
0: Setting dial 1(save even if
power is off)
1: Terminal board VIA
2: Terminal board VIB
3: Setting dial 2(press in center to
save)
4: RS485 communication
5: UP/DOWN from external logic
input
6: CANopen communication
7: Communication option
8: Terminal board VIC
9, 10: -
11: Pulse train input
0: fmod ( Switchable to f207
by the input terminal)
1: fmod ( f207 for output
frequencies equal to or lower
than 1.0 Hz)
F-13
Adjustment range
Default setting
E6581697
0
1
0
6