Toshiba TOSVERT VF-MB1 Instruction Manual page 106

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-MB1:
Table of Contents

Advertisement

:
:
No matter what value the command mode selection  and the frequency setting mode selection 1
 are set to the control input terminal functions described below are always in operative state.
 Reset terminal (valid only for tripping if set for programmable input terminal function)
 Standby terminal (when programmed by programmable input terminal functions).
 External input tripping stop terminal command (when so set using the programmable input terminal
function)
 Coast stop command terminal (if set for programmable input terminal function)
To make changes in the command mode selection  and the frequency setting mode selection 1
5
, first stop the inverter temporarily.
(Can be changed while in operation when  is set to .)
Priority commands from communications or terminal boards are given priority over .
 Preset-speed operation
: Set to  (Terminal board operation)
: Valid in all setting values.
 Input terminal settings
Assign the following functions to the input terminal to allow switching of the frequency command by turning
the terminal ON/OFF.
106
Each of the following numbers (49, 107) are reverse signals.
A frequency command is set by means of external analog signals.
Terminal board VIC
(VIC terminal: 0 (4) - 20mAdc)
⇒ Refer to section 3.2.2 and 7.3
A frequency command is set by means of external pulse train signals.
Pulse train input
(S2 terminal: 10pps - 20kpps)
⇒ Refer to section 6.6.5
Input terminal function
48
Forced local from communication
Frequency setting mode terminal
board
ON
Enabled during communication
Local (Setting of , )
Terminal board (VIA) enabled
E-12
E6581697
OFF
Communication
setting of 