Zone Function Settings / Zone Types - Bosch AMAX panel 4000 Installation Manual

Icp-amax4-p1 / icp-amax4-p2-en / icp-amax-p3-en
Hide thumbs Also See for AMAX panel 4000:
Table of Contents

Advertisement

AMAX panel 4000 / AMAX panel 4000
EN
Loop resistance (ohm)
Min
o
1650
2970
5220
Using one 2.2K resistor as EOL of the tamper zone, which works together with the zone EOL
2.2K. Refer to the drawing:
On -board Tamper Input
A separate input is provided for enclosure tamper (This is in addition to the 8 on-board total
inputs). The response time of the tamper input is a fixed zone response time. The tamper loop
will cause a siren alarm when the loop is open, and will be reported when the loop is open
(based the "system status report option").When powered up, the system will wait for 60
seconds to setup the normal work.
Tamper Switch connector Input:
Close: Normal
Open: Alarm Tamper Alarm process is the same as 24-Hour Alarm process (Onboard Tamper is
processed as zone number 17).
7.2.2

Zone Function Settings / Zone Types

Zone Types
Zone Function Option
Zone Type
Bosch Sicherheitsysteme GmbH
Type
2200
4400
COM
Z3
Description
00
Zone Not Used
01
Instant
02
Interior Instant
03
Delay
04
Interior Delay
Installation Guide
Zone Status
Max
1430
tamper
2750
normal
4950
triggered
tamper
1
2
Settings | en
47
2013.07 | 03 | F.01U.267.112