Bosch AMAX panel 4000 Installation Manual page 40

Icp-amax4-p1 / icp-amax4-p2-en / icp-amax-p3-en
Hide thumbs Also See for AMAX panel 4000:
Table of Contents

Advertisement

40
en | Settings
Communication path 1 fault will occur when path 1 and valid path 2 fail; communication path
1 fault will recover when fault 1 or 2 recovers.
Communication path 3 fault will occur when path 3 and valid path 4 fail; communication path
3 fault will recover when fault 3 or 4 recovers.
The attempt rules to send reports are as follows:
1 - Number and time of attempts to send report
When CID format or Conettix IP communication format is used for all, the order of priority of
attempts is path 1, 2, 3, 4, personal alarm telephone 1 - 4. The unused paths are ignored.
When a new event report occurs, the system will send reports in accordance with the
specified path.
For each reporting path used, the alarm control panel will repeatedly try until the report is
successfully sent.
For each reporting path used, the interval of the first 4 attempts is 15 seconds, the interval of
the fifth to eighth attempt is 10 seconds, and the interval afterwards is 60 seconds.
For each reporting path used (excluding personal telephone alarm), if a new event occurs, the
waiting time for the next retry will be cleared. If the newly-occurred event is communication
path fault, the previous retry logic will not be affected (the waiting time will not be cleared).
2 – The order of priority of attempts to send report
When CID format or Conettix IP communication format is used for all, the order of priority of
sending report is path 1, 2, 3, 4, personal alarm telephone 1 - 4. Some unused paths will be
ignored.
3 – Communication failure fault
When a report is still not successfully sent after the reporting path has been attempted for up
to 4 times, the system will generate the communication failure fault event of the path.
4 – Backup event
If an event is not successfully sent, the alarm control panel will provide a buffer to store up to
50 events. If more than 50 events are not successfully sent, only the last 50 events will be
stored in the buffer until the events are delivered. Other earlier events will be deleted.
5 - Display of faults
When multiple reports are queued for delivery, the communication path fault is displayed as
logic or relationship. Example:
Set zone status recovery report to send report to receiver 1; set keypad emergency report to
send report to receiver 1, with receiver 2, 3, 4 as backup.
Communication path fault is as follows: When communication paths 1, 2, 3, and 4 all fail, as
the communication path fault is displayed as logic or relationship, only the illumination of zone
indicator 1 expresses that the communication path 1 of the zone status recovery report fails
and the all communication paths 1, 2, 3 and 4 of the keypad emergency report fail as well.
Communication path fault recovery is as follows:
2013.07 | 03 | F.01U.267.112
If the event reporting path is set to sending report to receiver 1, receiver 2 as backup;
sending report to receiver 3, receiver 4 as backup; the alarm control panel will send
reports to corresponding paths.
Installation Guide