en | Settings
7.2

Zones

7.2.1

Zone Inputs

On-board Inputs:
There are 8 onboard hard-wired inputs for AMAX panel 4000 / AMAX panel 4000 EN. An
additional input is provided for enclosure tamper but does not subtract from the 8 onboard
totals.
On-board Zone Response Time:
Each on-board zone response time is:
Zone Status trigger time >= 400ms, must response
Zone Status trigger time < 300ms, no response
On board Zone EOL
1.
Loop Resistance (ohm)
Min
0
1650
2970
The detectors (sensors) will be connected between zone and COM terminal through EOL
series connection (open triggered) or EOL parallel connection (short triggered).
The detectors (sensors) will be connected between zone and COM terminal through EOL
series connection (open triggered) or EOL parallel connection (short triggered).
The panel sets the short/open as activate when connecting with single EOL.
The valid zone number is 1-8 for AMAX.
1.
2013.07 | 03 | F.01U.267.112
Single EOL: If zone tamper function is not selected, each zone uses a single 2.2k ohm
EOL. The panel can detect the zone as short, normal or open.
Type
2200
COM
Zone
COM
Zone
Dual EOL: If the tamper supervision is set, we only can use the NC contact point. The EOL
status is:
Max
1430
2750
Installation Guide
AMAX panel 4000 / AMAX panel 4000
Zone Status
triggered
normal
triggered