AMAX panel 4000 / AMAX panel 4000
EN
Zone Status Reporting and Zone Recovery Reporting
Alarm Report
In arming status, in case of alarm event, the alarm report will be sent.
Alarm Recovery Report
In arming status, when the zone recovers, the zone recovery report will be sent at the end of
alarm output time.
If the non-24-hour zone is not recovered in disarming, the system will automatically send a
zone recovery report. The 24-hour zone sends zone recovery report only when the zone
recovers.
Zone Fault Report
If the zone is in triggering status at the end of exit delay, a zone fault report will be sent,
indicating that the zone is automatically bypassed by the system. At the end of exit delay time,
the 24-hour zone in triggering status will not send zone fault report, i.e., the 24-hour zone will
not be automatically bypassed.
The non 24-hour zone fault recovery report will be sent when the zone recovers or the system
disarms. For the 24-hour zone, only the alarm recovery event will occur.
The zone fault occurs when the zone is triggered and recovers when the zone is normal. Zone
fault will occur when one of the following conditions is met:
Fault recovery conditions:
Zone Bypass Report
After the manual bypass zone is operated, the zone will be bypassed. The zone bypass report
will be sent at the end of exit delay time. The bypass report of the 24-hour zone will be sent
immediately after manual bypass operation.
The zone bypass will be recovered when the system is disarmed and the zone bypass recovery
report will also be sent while disarming.
Bosch Sicherheitsysteme GmbH
When communication path 1 fault recovers, zone indicator 1 goes off, indicating that the
communication path 1 fault of the zone status recovery report recovers and the
communication part 1 fault of the keypad emergency report recovers.
When any one path fault of communication paths 2, 3 and 4 recovers, as the
communication path fault is displayed as logic or relationship, zone indicator 1 still
illuminates, indicating that the communication path 1 fault of the zone status recovery
report has not be recovered, but the path fault of the keypad emergency report has been
recovered
For 24-hour zone, (internal) instant zone, if the forced arming option is set to allow, the
zone fault event will occur when the arming operation is executed while the zone is in
triggering status.
When the zone is locked.
For (internal) delay and (internal) follow zone, if they are still in triggering status at the
end of exit delay, zone fault event will occur.
For 24-hour zone, if it is in triggering status when the bypass is cancelled, zone fault
event will occur.
Zone resumes to normal conditions.
When the failed (internal) delay zone, (internal) instant zone and (internal) follow zone
are disarmed, the fault recovery event will occur even if the zone is still in triggering
status.