Table 4-4. Normally-Open REPO Connections and Wire Terminations
From REPO Station
Switch Contact
Block
UPS REPO
(Either Block)
Terminal
3 NO
3
4 NO
4
REPO
Switch
(NO)
NOTE
NOTE
Figure 4-19. Normally-Open REPO Switch Wiring
Table 4-5. Normally-Closed REPO Connections and Wire Terminations
From REPO Station
Switch Contact
Block
UPS REPO
(Either Block)
Terminal
3 NO
1
4 NO
2
REPO
Switch
(NC)
NOTE
NOTE
Figure 4-20. Normally-Closed REPO Switch Wiring
Eaton 93PM UPS (60–100 kW, 480V) Installation and Operation Manual P-164000227—Rev 2
Name
Description
EPO_A
Input: normally-open dry contact used to activate UPS EPO from
a remote switch.
EPO_B
3
Twisted
Wires
4
REPO switch rating is 24 Vdc, 1A minimum.
The REPO switch must be a latching-type switch not tied to any other circuits.
Name
Description
EPO_A_B
Input: normally-closed dry contact used to activate UPS EPO
from a remote switch.
GND-ISO
1
Twisted
Wires
2
REPO switch rating is 24 Vdc, 1A minimum.
The REPO switch must be a latching-type switch not tied to any other circuits.
1
2
REPO TB
3
4
1
2
REPO TB
3
4
www.eaton.com/powerquality
UPS System Installation
Wire Size
Tightening Torque
2 lb in
Twisted Pair Wires
(0.23 Nm)
#1630 AWG
Wire Size
Tightening Torque
2 lb in
Twisted Pair Wires
(0.23 Nm)
#1630 AWG