UPS Installation Plan and Unpacking

Table 3-1. UPS Cabinet Weights

Eaton 93PM-100 with UPS Top Entry Wiring Sidecar (no breakers)
Eaton 93PM-100 with four breaker Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B)
UPS Top Entry Wiring Sidecar (no breakers)
The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are on top or in the back of the cabinet. Allow clearance in front of and on top or in
back of the cabinet for proper air circulation. The clearances required around the UPS cabinet are shown in
Table 3-2.

Table 3-2. UPS Cabinet Clearances

From Front of Cabinet
From Top of Cabinet with Top Exhaust (Zones 1 and 3 – see Figure 3-2 ) 457.2 mm (18") minimum clearance for ventilation
From Top of Cabinet (Zones 2 and 3– see Figure 3-2 )
From Top of Cabinet with rear service access (Zone 2– see Figure 3-2) Can be less than 457.2 mm (18")
From Back of Cabinet with Rear Exhaust
From Back of Cabinet with Top Exhaust
From Right Side of Cabinet
From Left Side of Cabinet
The basic environmental requirements for operation of the UPS are:
Ambient Temperature Range: 5–40C (41–104F)
l
Recommended Operating Range: 5–40C (41–104F)
l
Maximum Relative Humidity: 95%, noncondensing
l
If battery systems are located in the same room as the UPS, the battery manufacturer's
environmental requirements should be followed if they are more stringent than the UPS
requirements. Operating temperatures above the recommended range will result in decreased
battery life and performance, and may reduce or void the battery warranty.
3-2
Eaton 93PM UPS (60–100 kW, 480V) Installation and Operation Manual P-164000227—Rev 2
Model
Eaton 93PM-100
Four breaker SIAC-B
Weight
Shipping
Installed
414 (912)
394 (869)
487 (1074)
465 (1024)
520 (1145)
496 (1094)
74 (162)
106 (233)
914.4 mm (36") working space
457.2 mm (18") working space
254 mm (10") minimum clearance for ventilation
None Required
None Required
None Required
CAUTION
www.eaton.com/powerquality
kg (lb)
Point Loading
4 at 98 (217)
4 at 117 (256)
5 at 99 (219)