UPS Operating Instructions
6.2.3

Using the LCD Touch Screen

The LCD touch screen on the control panel provides an operator interface with the UPS system. Figure 6-3
identifies the display areas discussed in the following sections.
All functions and commands are accessed by touching or tapping the screen tabs or buttons. When text input
is required, either a Qwerty keyboard or numeric keypad will be displayed.
A
B
C
D

Figure 6-3. Parts of the LCD

A
Status Bar displays the UPS name, UPS state, current date and time, meter information, active alarms
and notices, and a sign in/sign out button. For more information about alarms and notices, see paragraph
6.2.2.
B
Main Menu Navigation Bar displays main menu functions and selections as tab buttons. To select a
screen function touch the tab name.
C
Secondary Menu Navigation Bar displays functions and selections related to the current screen as tab
buttons. To select a screen function touch the tab name.
D
Information Area contains status data, operational controls, acknowledgments, action confirmations, and
screen prompts.
You can use the LCD touch screen to:
Look at a log of UPS events (alarms, notices, and commands) (see paragraph 6.2.6)
l
Monitor UPS operation (see paragraph 6.2.6)
l
Set UPS parameters (see paragraph 6.2.6)
l
Control UPS operation (see paragraphs 6.2.6 and 6.2.8)
l
6-4