Chapter 7

Communication

This chapter describes the communication features of the Eaton 93PM UPS. For terminal wiring information,
see paragraph 3.2.3 and paragraph 4.8. For location of the customer interface panel and terminals, see
Figure 4-11 and Figure 4-12.
7.1

Minislot Cards

The Eaton 93PM UPS has two standard, factory-installed Minislot communication bays. See Figure 4-11 for bay
locations. The UPS is compatible with the following Minislot cards (see Figure 7-1):
The Power Xpert
l
Eaton 93PM uninterruptible power systems (UPSs) through standard Web pages, Power Xpert software,
Intelligent Power Manager (IPM), Intelligent Power Protector (IPP), or third-party software. As an integral
part of the Eaton Power Xpert Architecture
to the Ethernet network.
Network managers can view critical downstream device information, such as status, power, energy, and
power quality data with an easy-to-use interface.
Industrial Relay Card-Minislot – can be used to indicate the operating status of the UPS system using the
l
customer's monitoring equipment. The Industrial Relay Card uses five isolated normally-open or
normally-closed dry relay contacts to indicate the UPS status. Normal, Bypass, Battery, and Alarm modes
can be monitored. One input can be activated by a switch or dry contact. The voltage source is provided by
the card, no external voltage source is needed.
For installation and setup of a Minislot card, contact an Eaton service representative (see paragraph 1.8). Refer
to the manual supplied with the Minislot card for user instructions.
Industrial Relay Card-Minislot

Figure 7-1. Optional Minislot Cards

7.2

Building Alarm Monitoring

This standard feature lets you connect the UPS to your building alarms, such as smoke detectors or
overtemperature alarms. The building alarm customer interface terminals for external are located inside the
UPS. Use twisted-pair wires for each alarm input and common.
The building alarms can be programmed to display the alarm functional name.
NOTE
Only one Power Xpert
®
Gateway Minislot (PXGMS) UPS Card provides Web-enabled, real-time monitoring of
Eaton 93PM UPS (60–100 kW, 480V) Installation and Operation Manual P-164000227—Rev 2
®
Gateway Minislot UPS Card can be used at one time.
®
, the PXGMS UPS Card provides a central point to connect UPSs
+
-