4 4 U U P P S S S S y y s s t t e e m m I I n n s s t t a a l l l l a a t t i i o o n n ....................................................5 5 3 3 4.1 Preliminary Installation Information....................... 53 4.2 Unloading the UPS Cabinet from the Pallet..................... 53 4.3 Integrated Battery Cabinet Installation......................57 Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 4
7.3.1 Starting the UPS in Double Conversion Mode ..................112 7.3.2 Starting the UPS in Bypass Mode......................113 7.3.3 Starting the UPMs ..........................113 7.3.4 Starting a Single UPM........................114 Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 5
9 9 U U P P S S M M a a i i n n t t e e n n a a n n c c e e ......................................................1 1 3 3 1 1 9.1 Important Safety Instructions ........................131 Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 6
1 1 1 1 W W a a r r r r a a n n t t y y ........................................................... . 1 1 3 3 9 9 11.1 Limited Factory Warranty for Three-Phase Eaton 93PM UPS and 93PM UPS Accessory Products ......139...
Page 7
Normally-Closed REPO Switch Wiring ....................84 Figure 38. Main Elements of the UPS System ....................87 Figure 39. Path of Current Through the UPS in Energy Saver System Mode............89 Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 8
Typical EAA Control Screen ......................112 Figure 66. REPO Operation ........................119 Figure 67. Optional Minislot Cards ....................... 127 Figure 68. Air Filter Location ........................133 viii Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
AC power to protect the customer's load from power failures. The Eaton 93PM, Four-Wire UPS online power protection system is used to prevent loss of valuable electronic information, minimize equipment downtime, and minimize the adverse effect on production equipment due to unexpected power problems.
1 1 . . 1 1 . . 4 4 E E n n e e r r g g y y S S a a v v e e r r S S y y s s t t e e m m M M o o d d e e The 93PM Series UPS offers an Energy Saver System (ESS) mode that maximizes efficiency by eliminating unnecessary power conversion when the commercial power source is within acceptable voltage and frequency limits.
UPS cabinet. The sidecar can be installed on the left or right side of the UPS cabinet. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
UPS from virtually any location within the facility, up to 300 feet from the UPS. Refer to the Eaton Remote Monitoring Device (RMD) Installation and Operation Manual, listed in paragraph 1.8 For More...
U U s s i i n n g g T T h h i i s s M M a a n n u u a a l l This manual describes how to install and operate the Eaton 93PM, Four-Wire UPS. Read and understand the procedures described in this manual to ensure trouble-free installation and operation.
F F o o r r M M o o r r e e I I n n f f o o r r m m a a t t i i o o n n Refer to the Eaton 93PM Integrated Battery Cabinet Installation Manual-Large and Large High Rate, the Eaton...
Page 18
1 1 . . 1 1 0 0 E E q q u u i i p p m m e e n n t t R R e e g g i i s s t t r r a a t t i i o o n n Please visit www.eaton.com/pq/register to register your new Eaton UPS / Eaton UPS Accessory. Model Number: Serial Number: Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 19
• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 20
Ne pas fumer près des accumulateurs. Ne pas produire de flamme ou d’étincelle dans la zone de l’accumulateur. Dissiper l'électricité statique de votre corps en touchant une surface reliée à la terre avant de toucher les accumulateurs. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Service Engineer, or the warranty terms specified in Chapter 11 Warranty become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (a minimum two-week notice is required) to reserve a preferred startup date.
To allow for future power upgrades, Eaton recommends using air conditioning or ventilation sized for the fully rated UPS kW frame size installed instead of the derated kW ordered. Sizing the site cooling infrastructure to be capable of cooling the maximum kW frame size will allow a full power rating upgrade without having to modify the infrastructure.
914.4 mm (36") working space From Back of Cabinet – Seismic Installation From Right Side of Cabinet None Required None Required From Left Side of Cabinet Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
UPS Installation Plan and Unpacking Figure 3. UPS Cabinet Dimensions (Front and Right Side Views) Front Right Side Dimensions are in millimeters [Inches] Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
UPS Installation Plan and Unpacking Figure 4. UPS Cabinet Dimensions (Top and Bottom Views) Front Bottom Front NOTE Top exhaust configuration shown Dimensions are in millimeters [Inches] Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
UPS with Sidecar Dimensions are in millimeters [inches] NOTE The UPS’ Front Floor Mounting Bracket’s mounting dimensions are identical to the Rear Floor Mounting Bracket dimensions. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
If wire is run in an ambient temperature greater than 40°C, larger size wire may be necessary. Wire sizes are based on using the specified breakers. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 33
With dual auxiliary MOBs, one UPM can be bypassed while the remaining UPMs support the load as long as the remaining UPMs have the capacity to do so. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
15. Wire sizes listed are for copper wiring only. IMPORTANT This product has been evaluated for use with copper wire only. For external wiring, use only 75°C copper wire. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
Page 39
Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
Page 45
Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
Page 48
Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
Conduit sizes listed are for copper wiring only. IMPORTANT This product has been evaluated for use with copper wire only. For external wiring, use only 75°C copper wire. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 54
If an output lockable disconnect is required, it is to be supplied by the customer. Table 19 Table 20 list the recommended rating for input and bypass circuit breakers. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required. Read and understand the following notes while planning and performing the installation: Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 59
Alarm relay contacts have a maximum current rating of 5A and a switched voltage rating of 30 Vac. • Alarm relay wiring should be a minimum of 18 AWG (recommended 18 AWG). Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 60
CAUTION Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately. NOTE For the following step, verify that the forklift or pallet jack is rated to handle the weight...
UPS Installation Plan and Unpacking Figure 13. UPS Cabinet with Left-Mounted or Right-Mounted Top Entry Wiring Sidecar as Shipped on Pallet UPS with Left-Mounted Sidecar UPS with Right-Mounted Sidecar Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 63
14. Place a floor protector from the parts kit underneath each jacking bolt, and screw the bolts down against them. The floor protectors protect the floor from being marred by the jacking bolts. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
3 mm (1/8") above the floor (just enough to allow the removal of the pallet skids). Failure to follow these instructions can result in serious injury or death. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
13. If a sidecar is attached to the UPS, remove the bottom screw securing the sidecar front panel. Lift the panel straight up to remove from the panel hanger brackets at the top of the cabinet. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 66
33. Locate the black cover dots from the parts kit and install over the left and right side bracket mounting holes. 34. Proceed to paragraph 4.3 Integrated Battery Cabinet Installation. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
S S i i d d e e c c a a r r I I n n t t e e g g r r a a t t e e d d A A c c c c e e s s s s o o r r y y C C a a b b i i n n e e t t - - B B y y p p a a s s s s W W i i r r i i n n g g I I n n s s t t a a l l l l a a t t i i o o n n If an SIAC-B is attached to the UPS, refer to the Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass Installation and Operation (50 kW and 100 kW SIAC-B) Manual, listed in paragraph 1.8 For More...
Page 68
Bypass mode. 14. Connect phase A, B, and C power wiring from the output terminals of each UPS to the tie cabinet. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Interface Wiring Bottom Entry Conduit Landing for AC Input and Output, and DC Input Bottom View NOTE: Remove panels to drill or punch conduit holes. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Left Side View Right Side View Inter-cabinet wiring access knockouts. Remove knockouts as required to route power wiring between cabinets. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
(A, B, C, N [if 4-wire]) AC Output to AC Input to Critical Load UPS Rectifier (A, B, C, N [if 4-wire]) (A, B, C) Front Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Reinstall all safety shield panels previously removed and secure with the retained hardware. If removed, reinstall the sidecar front panel and secure with the retained hardware. Close the UPS outside door and secure the latch. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Connections; if wiring REPO connections, proceed to paragraph 4.8 Installing a REPO Switch; otherwise, proceed to Step 16. 16. Close the UPS outside door and secure the latch. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Minislot Communication Bay 1 Minislot Communication Bay 4 Pull Chain and Host USB Relay Output Terminals CAN Terminals Device USB REPO Terminals Building Alarm Terminals RS-232 Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 79
14. Route the battery detect wiring from the battery cabinet through the top interface entry conduit landing plate to the UPS building alarm terminals. See Figure 17 for wiring access information, and Figure 22 Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 80
Figure 28 Figure 29 for UPS terminal locations. Refer to the Eaton 93PM Integrated Battery Cabinet Installation Manual-Large and Large High Rate or the Eaton Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 81
13. Reinstall all safety shield panels previously removed and secure with the retained hardware. 14. If removed, reinstall the sidecar front panel and secure with the retained hardware. 15. Close the UPS outside door and secure the latch. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Trip – Not Used Not Used Figure 30. Battery Shunt Trip Terminal Assignments Not Used Not Used Battery Shunt Trip - Battery Shunt Trip + Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 84
Connections; if wiring REPO connections, proceed to paragraph 4.8 Installing a REPO Switch; otherwise, proceed to Step 15. 15. Close the UPS outside door and secure the latch. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 85
Connections; if wiring REPO connections, proceed to paragraph 4.8 Installing a REPO Switch; otherwise, proceed to Step 17. 17. Close the UPS outside door and secure the latch. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Figure 32. External Parallel Terminal Block Pull Chain Ground_S CAN H In CAN L In External Ground (ISP) Parallel TB Earth CAN H Out CAN L Out Ground (ISP) Earth Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 88
16. If wiring Minislot connections, proceed to paragraph 4.7.7 Installing Minislot Interface Connections; if wiring REPO connections, proceed to paragraph 4.8 Installing a REPO Switch; otherwise, proceed to Step 17. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 90
15. If wiring REPO connections, proceed to paragraph 4.8 Installing a REPO Switch; otherwise, proceed to Step 16. 16. Close the UPS outside door and secure the latch. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 91
Proceed to Step 14. Remove the bottom interface entry conduit landing plate to drill or punch holes. 10. Reinstall the interface entry plate and install the conduit. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
34). The REPO switch wiring must be in accordance with NEC Article 725 Class 2 requirements. 18. Close the UPS outside door and secure the latch. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Eaton Customer Service Engineer, or the warranty terms specified in Chapter 11 Warranty become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (Optional) o Air conditioning equipment is installed and operating correctly. o The area around the installed UPS system is clean and dust-free. (Eaton recommends that the UPS be installed on a level floor suitable for computer or electronic equipment.) o Adequate workspace exists around the UPS and other cabinets.
Switchgear AC Input to Rectifier/ Charger Power Module Digital Metering AC Output Static AC Input to to Critical Bypass Switch Load Bypass Switchgear UPS Cabinet Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
The following paragraphs describe the differences in the UPS operating modes, using block diagrams to show the power flow during each mode of operation. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
NOTE Dashed lines indicate optional features/components. Breaker AC Input to rectifier is not used in single-feed configuration. External Battery Cabinet (Not supplied with the UPS.) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
SIDECAR External Battery NOTE Dashed lines indicate optional features/components. Cabinet AC Input to rectifier is not used in single-feed configuration. (Not supplied with the UPS.) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
UPM 1 External Battery NOTE Dashed lines indicate optional features/components. Cabinet AC Input to rectifier is not used in single-feed configuration. (Not supplied with the UPS.) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
UPS operation, see paragraph 7.2 Using the Control Panel. Figure 46. UPS Controls and Indicators Upper Front Door View Control Panel Door Latch Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
The four symbols on the bottom of the control panel are status indicators. These colored light emitting diode (LED) lamps work with the alarm horn to provide the operating status of the UPS. Table 31 describes the status indicators. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
This message is also written to the Events Log and may be added to the History Log. The messages are divided into four categories: alarms, notices, status, and commands. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
7.2.6 Display Menu Operation) • Set UPS parameters (see paragraph 7.2.6 Display Menu Operation) • Control UPS operation (see paragraphs 7.2.6 Display Menu Operation 7.2.8 System Controls) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
The Mimic screen shows the internal components of the UPS cabinet and a real-time graphical representation of the operating status of the system. Figure 49. Main Menu and Mimic Screen Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
The end of the log (the most recent events) is displayed first; scroll upward to view older event listings. To scroll through the events, press the up or down scroll bar. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Tap the desired statistic button to display the detailed statistic screen. Controls See paragraph 7.2.8 System Controls for details. Figure 50. Typical Meters Summary Screen Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
To prevent inadvertent or unauthorized power disruption to the critical load or auxiliary lighting system, change the Level 1 and Level 2 default passwords when system commissioning startup is performed. To Sign in: Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Level 1 default password is 1111. Settings Level 2 default password is 0101. Sign in is complete. Tap continue to return to previous screen. Figure 59. Sign In Password Screen Figure 60. Sign In Keypad Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Verify no alarms are active. Tap the CONTROLS tab on the main menu navigation bar. The System Control screen is displayed. Tap the GO ONLINE button. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 123
Double Conversion mode and supply the critical load. 10. Repeat Steps Step 5 through Step 8 selecting UPM 3 to start UPM 3. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 124
The UPS transfers to Double Conversion mode. If the power module is not available, the system remains on bypass and an alarm sounds. The NORMAL status indicator is illuminated. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 125
Step 5 selecting UPM 3 to shut down UPM 3. The UPM status indicates SHUTDOWN. The power module is turned off. Logic power remains on. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Tap the CONTROLS tab on the main menu navigation bar. The Control screen is displayed. Tap the UPS CONTROLS tab on the secondary navigation bar. The UPS Control screen is displayed. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Power is present inside the UPS cabinet until the upstream input feeder circuit breakers and battery breakers are opened. Wait at least 5 minutes before accessing internal components. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 128
Power is present inside the UPS cabinet until the upstream input feeder circuit breakers and battery breakers are opened. Wait at least 5 minutes before accessing internal components. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Power is now supplied to the critical load in dual conversion mode from all UPSs. It takes approximately one minute for the UPSs to achieve the dual conversion mode. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 130
Double Conversion mode and supply the critical load. 11. Repeat Steps Step 1 through Step 10 for each UPS in the parallel system. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 131
7 7 . . 4 4 . . 7 7 T T r r a a n n s s f f e e r r f f r r o o m m E E S S S S M M o o d d e e t t o o D D o o u u b b l l e e C C o o n n v v e e r r s s i i o o n n M M o o d d e e To transfer the load to Standard Normal mode: Tap the CONTROLS tab on the main menu navigation bar. The Control screen is displayed. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 132
Tap the MODULES CONTROLS tab on the secondary Control menu navigation bar. The UPM Select screen is displayed. On the UPM Select screen, select the UPM to shutdown. The UPM Control Screen is displayed. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 133
On the UPS being restarted, tap the CONTROLS tab on the main menu navigation bar. The System Control screen is displayed. Tap the GO ONLINE button. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Tap the CONTROLS tab on the main menu navigation bar. The Control screen is displayed. Tap the UPS CONTROLS tab on the secondary navigation bar. The UPS Control screen is displayed. Tap the TURN OFF CHARGER button. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Power is present inside the UPS cabinet until the upstream input feeder circuit breakers and battery breakers are opened. Wait at least 5 minutes before accessing internal components. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 136
Power is present inside the UPS cabinet until the upstream input feeder circuit breakers and battery breakers are opened. Wait at least 5 minutes before accessing internal components. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
IRC-MS installation guide. One input can be activated by a switch or dry contact. The voltage source is provided by the card, no external voltage source is needed. For installation and setup of a Minislot card, contact an Eaton service representative. Refer to the manual supplied with the Minislot card for user instructions.
It’s also powered by CA Technologies, bringing together the best in hardware and software. PredictPulse Service is included at no charge during the first year of Eaton 93PM UPS operation (warranty period) along with the required connectivity parts. Beyond that, it may be purchased with Eaton Support Agreements or as a standalone subscription after the initial warranty expires.
Page 139
Real-time alarm events for all subscribed devices via the PredictPulse mobile app (Apple and Android). You can track all alarms by device. As critical alarms occur, Eaton will acknowledge them so you know when Eaton has diagnosed the alarm (and pending notification of resolution).
Page 140
Communication Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 141
The UPS system requires very little preventive maintenance. However, the system should be inspected periodically to verify that the units are operating normally and that the batteries are in good condition. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 142
The foam filters are to be replaced with new or washed filter immediately. The UPS is not meant to be run without filters installed. Close the front door and secure the latch Record maintenance results and any corrective actions in a suitable log. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
9 9 . . 2 2 . . 5 5 B B A A T T T T E E R R Y Y M M a a i i n n t t e e n n a a n n c c e e Contact an Eaton service representative for battery maintenance. Battery replacement and maintenance should be performed only by authorized service personnel. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Phillips and Pozidriv are registered trademarks of Phillips Screw Company. A basic training course, available from Eaton, gives you a competent working knowledge of the UPS system Copyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
1 1 0 0 . . 2 2 S S p p e e c c i i f f i i c c a a t t i i o o n n s s The following sections detail the input, output, environmental, and battery specifications for the UPS. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
< 2.5° for 100% maximum load imbalance (linear load) Frequency Regulation 0.1 Hz free running Synchronous to Bypass ± 4 Hz (default setting) Frequency Slew Rate 1 Hz per second (default setting) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 147
Meets IEC 61000-4-2 Level 3 specifications. Withstands up to 4 kV contact pulse without damage and with no disturbance or adverse effect to the critical load. Immunity Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
Page 149
For Product installed (and currently located) outside the fifty (50) United States and the District of Columbia, if, in the opinion of Eaton, a Warranted Item is defective, Eaton's sole obligation, at the option of Eaton, will be to refurbish or replace such defective Warranted Item (not including the costs of labor coverage). The defective Warranted Item will be refurbished or replaced onsite at the End-User's location or such other location as determined by Eaton.
Page 150
Eaton shall not be responsible for failure to provide service or parts due to causes beyond Eaton's reasonable control. In no case will Eaton's liability under this Warranty exceed the replacement value of the Warranted Items.