Eaton 93PM Installation And Operation Manual
Eaton 93PM Installation And Operation Manual

Eaton 93PM Installation And Operation Manual

400v/480v four-wire 100 kw frame
Table of Contents

Advertisement

Eaton
® ®
93PM UPS
400V/480V Four-Wire – 100 kW Frame
Installation and Operation Manual
p/n: 164000566
Revision 04

Advertisement

Table of Contents
loading

Summary of Contents for Eaton 93PM

  • Page 1 Eaton ® ® 93PM UPS 400V/480V Four-Wire – 100 kW Frame Installation and Operation Manual p/n: 164000566 Revision 04...
  • Page 2 National Fire Protection Association, Inc. ERIFLEX and FLEXIBAR are registered trademark of Erico International Corporation. All other trademarks are property of their respective companies. ©Copyright 2019 Eaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton.
  • Page 3: Table Of Contents

    4 4 U U P P S S S S y y s s t t e e m m I I n n s s t t a a l l l l a a t t i i o o n n ....................................................5 5 3 3 4.1 Preliminary Installation Information....................... 53 4.2 Unloading the UPS Cabinet from the Pallet..................... 53 4.3 Integrated Battery Cabinet Installation......................57 Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 4 7.3.1 Starting the UPS in Double Conversion Mode ..................112 7.3.2 Starting the UPS in Bypass Mode......................113 7.3.3 Starting the UPMs ..........................113 7.3.4 Starting a Single UPM........................114 Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 5 9 9 U U P P S S M M a a i i n n t t e e n n a a n n c c e e ......................................................1 1 3 3 1 1 9.1 Important Safety Instructions ........................131 Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 6 1 1 1 1 W W a a r r r r a a n n t t y y ........................................................... . 1 1 3 3 9 9 11.1 Limited Factory Warranty for Three-Phase Eaton 93PM UPS and 93PM UPS Accessory Products ......139...
  • Page 7 Normally-Closed REPO Switch Wiring ....................84 Figure 38. Main Elements of the UPS System ....................87 Figure 39. Path of Current Through the UPS in Energy Saver System Mode............89 Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 8 Typical EAA Control Screen ......................112 Figure 66. REPO Operation ........................119 Figure 67. Optional Minislot Cards ....................... 127 Figure 68. Air Filter Location ........................133 viii Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 9 Table 36. IRC-MS Default Triggers ....................... 127 Table 37. Eaton 93PM 400V UPS Models ...................... 135 Table 38. Eaton 93PM 480V UPS Models ...................... 135 Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 10: List Of Tables

    List of Tables Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 11: Ups Standard Features

    AC power to protect the customer's load from power failures. The Eaton 93PM, Four-Wire UPS online power protection system is used to prevent loss of valuable electronic information, minimize equipment downtime, and minimize the adverse effect on production equipment due to unexpected power problems.
  • Page 12: Figure 1. Eaton 93Pm Ups

    Figure 1. Eaton 93PM UPS Figure 2. Eaton 93PM UPS with Left or Right-Mounted Top Entry Wiring Sidecar UPS with Left-Mounted Sidecar UPS with Right-Mounted Sidecar Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 13: Control Panel

    1 1 . . 1 1 . . 4 4 E E n n e e r r g g y y S S a a v v e e r r S S y y s s t t e e m m M M o o d d e e The 93PM Series UPS offers an Energy Saver System (ESS) mode that maximizes efficiency by eliminating unnecessary power conversion when the commercial power source is within acceptable voltage and frequency limits.
  • Page 14: Integrated Battery Cabinet

    UPS cabinet. The sidecar can be installed on the left or right side of the UPS cabinet. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 15: Integrated Accessory Cabinet-Power Distribution

    UPS from virtually any location within the facility, up to 300 feet from the UPS. Refer to the Eaton Remote Monitoring Device (RMD) Installation and Operation Manual, listed in paragraph 1.8 For More...
  • Page 16: Battery System

    U U s s i i n n g g T T h h i i s s M M a a n n u u a a l l This manual describes how to install and operate the Eaton 93PM, Four-Wire UPS. Read and understand the procedures described in this manual to ensure trouble-free installation and operation.
  • Page 17: For More Information

    F F o o r r M M o o r r e e I I n n f f o o r r m m a a t t i i o o n n Refer to the Eaton 93PM Integrated Battery Cabinet Installation Manual-Large and Large High Rate, the Eaton...
  • Page 18 1 1 . . 1 1 0 0 E E q q u u i i p p m m e e n n t t R R e e g g i i s s t t r r a a t t i i o o n n Please visit www.eaton.com/pq/register to register your new Eaton UPS / Eaton UPS Accessory. Model Number: Serial Number: Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 19 • Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 20 Ne pas fumer près des accumulateurs. Ne pas produire de flamme ou d’étincelle dans la zone de l’accumulateur. Dissiper l'électricité statique de votre corps en touchant une surface reliée à la terre avant de toucher les accumulateurs. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 21: Preparing The Site

    Service Engineer, or the warranty terms specified in Chapter 11 Warranty become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (a minimum two-week notice is required) to reserve a preferred startup date.
  • Page 22: Table 1. Air Conditioning Or Ventilation Requirements During Full Load Operation (400V)

    To allow for future power upgrades, Eaton recommends using air conditioning or ventilation sized for the fully rated UPS kW frame size installed instead of the derated kW ordered. Sizing the site cooling infrastructure to be capable of cooling the maximum kW frame size will allow a full power rating upgrade without having to modify the infrastructure.
  • Page 23: Table 3. Ups Cabinet Weights

    Eaton 93PM-100-2 UPS with Left or Right-Mounted 4-Breaker SIAC-B 550 (1213) 527 (1162) 4 at 291 (291) Eaton 93PM-100-3 UPS with Left or Right-Mounted 4-Breaker SIAC-B 614 (1354) 591(1303) 4 at 148 (326) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 24: Table 4. Ups Cabinet Clearances

    914.4 mm (36") working space From Back of Cabinet – Seismic Installation From Right Side of Cabinet None Required None Required From Left Side of Cabinet Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 25: Figure 3. Ups Cabinet Dimensions (Front And Right Side Views)

    UPS Installation Plan and Unpacking Figure 3. UPS Cabinet Dimensions (Front and Right Side Views) Front Right Side Dimensions are in millimeters [Inches] Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 26: Figure 4. Ups Cabinet Dimensions (Top And Bottom Views)

    UPS Installation Plan and Unpacking Figure 4. UPS Cabinet Dimensions (Top and Bottom Views) Front Bottom Front NOTE Top exhaust configuration shown Dimensions are in millimeters [Inches] Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 27: Figure 5. Ups Cabinet Front And Back Floor Mounting Bracket Mounting Dimensions (Back Views)

    UPS with Sidecar Dimensions are in millimeters [inches] NOTE The UPS’ Front Floor Mounting Bracket’s mounting dimensions are identical to the Rear Floor Mounting Bracket dimensions. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 28: Figure 6. Ups Cabinet With Left Or Right-Mounted Sidecar Dimensions (Front Views)

    1880 [ 74.0 ] [ 30.0 ] [ 30.0 ] Front Front UPS With Left-Mounted Sidecar UPS With Right-Mounted Sidecar Dimensions are in millimeterse [Inches] Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 29: Figure 7. Ups Cabinet With Left Or Right-Mounted Sidecar Dimensions (Top And Bottom Views)

    [ 30.0 ] [ 30.0 ] Front Front 1067 Bottom Bottom [42.0] UPS With Left-Mounted Sidecar UPS With Right-Mounted Sidecar Dimensions are in millimeters [Inches] Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 30: Figure 8. Ups Cabinet Center Of Gravity

    274 (10.7) 361 (797) Eaton 93PM-100-2 UPS 907 (35.7) 537 (21.1) 275 (10.8) 425 (937) Eaton 93PM-100-3 UPS 1006 (39.6) 537 (21.1) 275 (10.8) 489 (1078) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 31: Figure 9. Ups Cabinet With Left Or Right-Mounted Sidecar Center Of Gravity

    Eaton 93PM-100-2 UPS with four breaker SIAC-B 913 (35.9) 568 (22.3) 354 (13.9) 527 (1162) Eaton 93PM-100-3 UPS with four breaker SIAC-B 995 (39.1) 564 (22.2) 346 (13.6) 591(1303) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 32: Figure 10. Remote Epo Switch Dimensions

    If wire is run in an ambient temperature greater than 40°C, larger size wire may be necessary. Wire sizes are based on using the specified breakers. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 33 With dual auxiliary MOBs, one UPM can be bypassed while the remaining UPMs support the load as long as the remaining UPMs have the capacity to do so. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 34: Figure 11. 93Pm External Parallel Wire Length

    15. Wire sizes listed are for copper wiring only. IMPORTANT This product has been evaluated for use with copper wire only. For external wiring, use only 75°C copper wire. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 35: Table 5. Input/Output Ratings And External Wiring Recommendations: Eaton 93Pm 20–40 Kw (380V)

    (3) Phases, (1) Neutral – see Note, (1) Ground Minimum Conductor Size (Phase A, B, C, and Neutral) AWG or kcmil (each) Number per Phase Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 36: Table 6. Input/Output Ratings And External Wiring Recommendations: Eaton 93Pm 50–80 Kw (380V)

    Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
  • Page 37: Table 7. Input/Output Ratings And External Wiring Recommendations: Eaton 93Pm 90–100 Kw (380V)

    Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
  • Page 38: Table 8. Input/Output Ratings And External Wiring Recommendations: Eaton 93Pm 20–40 Kw (400V)

    Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
  • Page 39 Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
  • Page 40: Table 9. Input/Output Ratings And External Wiring Recommendations: Eaton 93Pm 50–80 Kw (400V)

    (3) Phases, (1) Neutral – see Note, (1) Ground Minimum Conductor Size (Phase A, B, C, and AWG or kcmil Neutral) (each) Number per Phase Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 41: Table 10. Input/Output Ratings And External Wiring Recommendations: Eaton 93Pm 90–100 Kw (400V)

    Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
  • Page 42: Table 11. Input/Output Ratings And External Wiring Recommendations: Eaton 93Pm 20–40 Kw (415V)

    Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
  • Page 43: Table 12. Input/Output Ratings And External Wiring Recommendations: Eaton 93Pm 50–80 Kw (415V)

    Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
  • Page 44: Table 13. Input/Output Ratings And External Wiring Recommendations: Eaton 93Pm 90–100 Kw (415V)

    Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
  • Page 45 Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
  • Page 46: Table 14. Input/Output Ratings And External Wiring Recommendations: Eaton 93Pm 20–50 Kw (480V)

    (3) Phases, (1) Neutral – see Note, (1) Ground Minimum Conductor Size (Phase A, B, and C, and AWG or kcmil Neutral) (each) Number per Phase Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 47: Table 15. Input/Output Ratings And External Wiring Recommendations: Eaton 93Pm 60–100 Kw (480V)

    Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
  • Page 48 Chapter 6 UPS Oneline Schematics. Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC). The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA...
  • Page 49: Table 16. Ups External Power Cable Terminations

    Conduit sizes listed are for copper wiring only. IMPORTANT This product has been evaluated for use with copper wire only. For external wiring, use only 75°C copper wire. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 50: Table 17. Power Cable Conduit Recommendations (400V)

    400 Vac (A, B, C, Neutral, Ground) 50 kW 93PM-100-3 (N+1) 415 Vac AC Output 1-1/4 (A, B, C, Neutral, Ground Battery 1-1/2 (Positive, Negative, Ground) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 51 400 Vac (A, B, C, Neutral, Ground) 93PM-100-2 415 Vac 90 kW 93PM-100-3 (N+1) AC Output (A, B, C, Neutral, Ground Battery 1-1/2 (Positive, Negative, Ground) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 52: Table 18. Power Cable Conduit Recommendations (480V)

    480 Vac (A, B, C, Neutral, Ground 93PM-100-1 30 kW 93PM-100-2 (N+1) 1-1/4 AC Output (A, B, C, Neutral, Ground) 1-1/2 Battery (Positive, Negative, Ground) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 53 AC Input to UPS Bypass 480 Vac (A, B, C, Neutral, Ground 93PM-100-2 70 kW 93PM-100-3 (N+1) AC Output (A, B, C, Neutral, Ground) 1-1/2 Battery (Positive, Negative, Ground) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 54 If an output lockable disconnect is required, it is to be supplied by the customer. Table 19 Table 20 list the recommended rating for input and bypass circuit breakers. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 55: Table 19. Recommended Input And Bypass Circuit Breaker Ratings (400V)

    80% Rated 100A Eaton 93PM-100-1 50 kW Eaton 93PM-100-2 (N+1) 100% Rated 80% Rated 125A Eaton 93PM-100-2 60 kW Eaton 93PM-100-3 (N+1) 100% Rated 100A Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 56: Table 21. Recommended Output Circuit Breaker Ratings (400V)

    100A Eaton 93PM-100-2 50 kW Eaton 93PM-100-3 (N+1) 100% Rated 80% Rated 125A 110A 110A Eaton 93PM-100-2 60 kW Eaton 93PM-100-3 (N+1) 100% Rated 100A Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 57: Table 22. Recommended Output Circuit Breaker Ratings (480V)

    100% Rated 110A 80% Rated 150A Eaton 93PM-100-2 100 kW Eaton 93PM-100-3 (N+1) 100% Rated 125A There is no manual DC disconnect device within the UPS. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 58: Table 23. Recommended Dc Input Battery Disconnect Circuit Breaker Ratings

    Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required. Read and understand the following notes while planning and performing the installation: Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 59 Alarm relay contacts have a maximum current rating of 5A and a switched voltage rating of 30 Vac. • Alarm relay wiring should be a minimum of 18 AWG (recommended 18 AWG). Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 60 CAUTION Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately. NOTE For the following step, verify that the forklift or pallet jack is rated to handle the weight...
  • Page 61: Figure 12. Ups Cabinet As Shipped On Pallet

    UPS Installation Plan and Unpacking Figure 12. UPS Cabinet as Shipped on Pallet Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 62: Figure 13. Ups Cabinet With Left-Mounted Or Right-Mounted Top Entry Wiring Sidecar As Shipped On Pallet

    UPS Installation Plan and Unpacking Figure 13. UPS Cabinet with Left-Mounted or Right-Mounted Top Entry Wiring Sidecar as Shipped on Pallet UPS with Left-Mounted Sidecar UPS with Right-Mounted Sidecar Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 63 14. Place a floor protector from the parts kit underneath each jacking bolt, and screw the bolts down against them. The floor protectors protect the floor from being marred by the jacking bolts. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 64: Figure 14. Removing The Pallet Skids And Supports – Eaton 93Pm Ups

    3 mm (1/8") above the floor (just enough to allow the removal of the pallet skids). Failure to follow these instructions can result in serious injury or death. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 65: Figure 15. Removing The Sidecar Pallet Skids And Supports – Eaton 93Pm Ups

    13. If a sidecar is attached to the UPS, remove the bottom screw securing the sidecar front panel. Lift the panel straight up to remove from the panel hanger brackets at the top of the cabinet. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 66 33. Locate the black cover dots from the parts kit and install over the left and right side bracket mounting holes. 34. Proceed to paragraph 4.3 Integrated Battery Cabinet Installation. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 67: 4.4 Sidecar Integrated Accessory Cabinet-Bypass Wiring Installation

    S S i i d d e e c c a a r r I I n n t t e e g g r r a a t t e e d d A A c c c c e e s s s s o o r r y y C C a a b b i i n n e e t t - - B B y y p p a a s s s s W W i i r r i i n n g g I I n n s s t t a a l l l l a a t t i i o o n n If an SIAC-B is attached to the UPS, refer to the Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass Installation and Operation (50 kW and 100 kW SIAC-B) Manual, listed in paragraph 1.8 For More...
  • Page 68 Bypass mode. 14. Connect phase A, B, and C power wiring from the output terminals of each UPS to the tie cabinet. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 69: Battery Power Wiring

    (Remove panel to drill or punch conduit holes.) Front Bottom View Top Entry Conduit Landings for Customer Interface Wiring (Remove panels to drill or punch conduit holes.) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 70: Figure 18. Sidecar Conduit And Wire Entry Locations

    Interface Wiring Bottom Entry Conduit Landing for AC Input and Output, and DC Input Bottom View NOTE: Remove panels to drill or punch conduit holes. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 71: Figure 19. Ups Inter-Cabinet Wiring Access Location

    Left Side View Right Side View Inter-cabinet wiring access knockouts. Remove knockouts as required to route power wiring between cabinets. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 72: Figure 20. Power Terminal Locations

    (A, B, C, N [if 4-wire]) AC Output to AC Input to Critical Load UPS Rectifier (A, B, C, N [if 4-wire]) (A, B, C) Front Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 73: Installing Interface Connections

    Reinstall all safety shield panels previously removed and secure with the retained hardware. If removed, reinstall the sidecar front panel and secure with the retained hardware. Close the UPS outside door and secure the latch. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 74: Installing Battery Detect Interface Connections

    Connections; if wiring REPO connections, proceed to paragraph 4.8 Installing a REPO Switch; otherwise, proceed to Step 16. 16. Close the UPS outside door and secure the latch. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 75: Figure 22. Interface Terminal Locations

    Minislot Communication Bay 1 Minislot Communication Bay 4 Pull Chain and Host USB Relay Output Terminals CAN Terminals Device USB REPO Terminals Building Alarm Terminals RS-232 Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 76: Figure 24. Bottom Access Interface Wiring Location

    UPS System Installation Figure 24. Bottom Access Interface Wiring Location Wire Tie Anchors Bottom Access Interface Wiring Channel Bottom Entry Conduit Landings for Customer Interface Wiring Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 77: Figure 25. Wire Tie Anchors

    Building Alarm 4 closure Return Building Alarm 5 Input: Programmable UPS alarm, activated by a remote dry contact Building Alarm 5 closure Return Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 78: Figure 26. Building Alarm Terminal Block Connector Assignments

    Relay Contact NO Output: General purpose normally- Relay Contact closed (NO) relay contact Common Figure 27. Relay Contact Terminal Block Connector Assignments UPS Relay Output NC_Out NO_Out Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 79 14. Route the battery detect wiring from the battery cabinet through the top interface entry conduit landing plate to the UPS building alarm terminals. See Figure 17 for wiring access information, and Figure 22 Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 80 Figure 28 Figure 29 for UPS terminal locations. Refer to the Eaton 93PM Integrated Battery Cabinet Installation Manual-Large and Large High Rate or the Eaton Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 81 13. Reinstall all safety shield panels previously removed and secure with the retained hardware. 14. If removed, reinstall the sidecar front panel and secure with the retained hardware. 15. Close the UPS outside door and secure the latch. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 82: Figure 28. Battery Shunt Trip Locations

    UPS System Installation Figure 28. Battery Shunt Trip Locations Shunt Trip Terminals Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 83: Figure 29. Battery Shunt Trip Terminal Detail

    Trip – Not Used Not Used Figure 30. Battery Shunt Trip Terminal Assignments Not Used Not Used Battery Shunt Trip - Battery Shunt Trip + Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 84 Connections; if wiring REPO connections, proceed to paragraph 4.8 Installing a REPO Switch; otherwise, proceed to Step 15. 15. Close the UPS outside door and secure the latch. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 85 Connections; if wiring REPO connections, proceed to paragraph 4.8 Installing a REPO Switch; otherwise, proceed to Step 17. 17. Close the UPS outside door and secure the latch. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 86: Table 27. External Parallel Can And Pull Chain Connections

    0.4 (3.5) - 0.8 (7.1) Slotted Use twisted-pair wires for each input and return or common. Strip wire insulation back 10 millimeters to wire terminal blocks. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 87: Figure 31. External Parallel Can Wiring

    Figure 32. External Parallel Terminal Block Pull Chain Ground_S CAN H In CAN L In External Ground (ISP) Parallel TB Earth CAN H Out CAN L Out Ground (ISP) Earth Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 88 16. If wiring Minislot connections, proceed to paragraph 4.7.7 Installing Minislot Interface Connections; if wiring REPO connections, proceed to paragraph 4.8 Installing a REPO Switch; otherwise, proceed to Step 17. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 89: Figure 33. External Parallel Pull Chain Wiring

    Pull Chain Pull Chain Pull Chain Twisted Twisted Twisted Twisted Pair Pair Pair Pair UPS 1 UPS 2 UPS 3 UPS 4 (If Installed) (If Installed) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 90 15. If wiring REPO connections, proceed to paragraph 4.8 Installing a REPO Switch; otherwise, proceed to Step 16. 16. Close the UPS outside door and secure the latch. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 91 Proceed to Step 14. Remove the bottom interface entry conduit landing plate to drill or punch holes. 10. Reinstall the interface entry plate and install the conduit. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 92: Figure 34. Repo Switch

    34). The REPO switch wiring must be in accordance with NEC Article 725 Class 2 requirements. 18. Close the UPS outside door and secure the latch. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 93: Figure 35. Repo Terminal Block Connector Assignments

    UPS EPO from a remote Wires #18 0.25 Nm) #30 AWG 4 NO EPO_ switch Figure 36. Normally-Open REPO Switch Wiring REPO TB Twisted REPO Wires Switch (NO) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 94: Figure 37. Normally-Closed Repo Switch Wiring

    Eaton Customer Service Engineer, or the warranty terms specified in Chapter 11 Warranty become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
  • Page 95: Installation Checklist

    Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (Optional) o Air conditioning equipment is installed and operating correctly. o The area around the installed UPS system is clean and dust-free. (Eaton recommends that the UPS be installed on a level floor suitable for computer or electronic equipment.) o Adequate workspace exists around the UPS and other cabinets.
  • Page 96 UPS System Installation Notes: _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 97: Figure 38. Main Elements Of The Ups System

    Switchgear AC Input to Rectifier/ Charger Power Module Digital Metering AC Output Static AC Input to to Critical Bypass Switch Load Bypass Switchgear UPS Cabinet Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 98: Single Ups

    The following paragraphs describe the differences in the UPS operating modes, using block diagrams to show the power flow during each mode of operation. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 99: Energy Saver System Mode

    Switch Rectifier Input Output Rectifier Inverter Rectifier Inverter Switchgear Switchgear Battery Converter Main Power Flow Battery Switchgear Switchgear Trickle Current Closed Energized Open De-Energized Battery Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 100: Figure 40. Path Of Current Through The Ups In Normal Mode

    Switch Rectifier Input Output Rectifier Inverter Rectifier Inverter Switchgear Switchgear Battery Converter Main Power Flow Battery Switchgear Switchgear Trickle Current Closed Energized Open De-Energized Battery Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 101: Bypass Mode

    Switch Rectifier Input Output Rectifier Inverter Rectifier Inverter Switchgear Switchgear Battery Converter Main Power Flow Battery Switchgear Switchgear Trickle Current Closed Energized Open De-Energized Battery Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 102: Figure 42. Path Of Current Through The Ups In Battery Mode

    Switch Rectifier Input Output Rectifier Inverter Rectifier Inverter Switchgear Switchgear Battery Converter Main Power Flow Battery Switchgear Switchgear Trickle Current Closed Energized Open De-Energized Battery Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 103: Figure 43. Eaton 93Pm Four-Wire Ups System Oneline

    NOTE Dashed lines indicate optional features/components. Breaker AC Input to rectifier is not used in single-feed configuration. External Battery Cabinet (Not supplied with the UPS.) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 104: Figure 44. Eaton 93Pm Four-Wire Ups With Top Entry Sidecar System Oneline

    SIDECAR External Battery NOTE Dashed lines indicate optional features/components. Cabinet AC Input to rectifier is not used in single-feed configuration. (Not supplied with the UPS.) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 105: Figure 45. Eaton 93Pm Four-Wire Ups With Bypass Sidecar (Siac-B) System Oneline

    UPM 1 External Battery NOTE Dashed lines indicate optional features/components. Cabinet AC Input to rectifier is not used in single-feed configuration. (Not supplied with the UPS.) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 106 UPS Oneline Schematics Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 107: Using The Control Panel

    UPS operation, see paragraph 7.2 Using the Control Panel. Figure 46. UPS Controls and Indicators Upper Front Door View Control Panel Door Latch Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 108: Status Indicators

    The four symbols on the bottom of the control panel are status indicators. These colored light emitting diode (LED) lamps work with the alarm horn to provide the operating status of the UPS. Table 31 describes the status indicators. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 109: Display Menu Operation

    This message is also written to the Events Log and may be added to the History Log. The messages are divided into four categories: alarms, notices, status, and commands. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 110: Figure 48. Parts Of The Lcd

    7.2.6 Display Menu Operation) • Set UPS parameters (see paragraph 7.2.6 Display Menu Operation) • Control UPS operation (see paragraphs 7.2.6 Display Menu Operation 7.2.8 System Controls) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 111: Figure 49. Main Menu And Mimic Screen

    The Mimic screen shows the internal components of the UPS cabinet and a real-time graphical representation of the operating status of the system. Figure 49. Main Menu and Mimic Screen Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 112: Display Menu Operation

    The end of the log (the most recent events) is displayed first; scroll upward to view older event listings. To scroll through the events, press the up or down scroll bar. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 113: Figure 50. Typical Meters Summary Screen

    Tap the desired statistic button to display the detailed statistic screen. Controls See paragraph 7.2.8 System Controls for details. Figure 50. Typical Meters Summary Screen Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 114: Figure 51. Typical Active Events Screen

    UPS Operating Instructions Figure 51. Typical Active Events Screen Figure 52. Typical System Log Screen Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 115: Figure 53. Typical Settings User Screen

    UPS Operating Instructions Figure 53. Typical Settings User Screen Figure 54. Typical Information Screen Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 116: Figure 55. Typical About Screen

    UPS Operating Instructions Figure 55. Typical About Screen Figure 56. Typical Settings Configuration 1 Screen Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 117: Sign In

    To prevent inadvertent or unauthorized power disruption to the critical load or auxiliary lighting system, change the Level 1 and Level 2 default passwords when system commissioning startup is performed. To Sign in: Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 118: Figure 59. Sign In Password Screen

    Level 1 default password is 1111. Settings Level 2 default password is 0101. Sign in is complete. Tap continue to return to previous screen. Figure 59. Sign In Password Screen Figure 60. Sign In Keypad Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 119: System Controls

    RUN BATTERY TEST starts the battery test. Table 35. Typical System Status Messages Message Function Double Conversion; Bypass; ESS Bypass Off; On; Available Charger Charger Resting; Charger Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 120: Figure 61. Typical System Control Screen

    UPS Operating Instructions Figure 61. Typical System Control Screen Figure 62. Typical UPS Control Screen Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 121: Figure 63. Typical Upm Select Screen

    UPS Operating Instructions Figure 63. Typical UPM Select Screen Figure 64. Typical UPM Control Screen Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 122: Figure 65. Typical Eaa Control Screen

    Verify no alarms are active. Tap the CONTROLS tab on the main menu navigation bar. The System Control screen is displayed. Tap the GO ONLINE button. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 123 Double Conversion mode and supply the critical load. 10. Repeat Steps Step 5 through Step 8 selecting UPM 3 to start UPM 3. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 124 The UPS transfers to Double Conversion mode. If the power module is not available, the system remains on bypass and an alarm sounds. The NORMAL status indicator is illuminated. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 125 Step 5 selecting UPM 3 to shut down UPM 3. The UPM status indicates SHUTDOWN. The power module is turned off. Logic power remains on. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 126: Charger Control

    Tap the CONTROLS tab on the main menu navigation bar. The Control screen is displayed. Tap the UPS CONTROLS tab on the secondary navigation bar. The UPS Control screen is displayed. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 127: 7.3.1 Starting The Ups In Double Conversion Mode

    Power is present inside the UPS cabinet until the upstream input feeder circuit breakers and battery breakers are opened. Wait at least 5 minutes before accessing internal components. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 128 Power is present inside the UPS cabinet until the upstream input feeder circuit breakers and battery breakers are opened. Wait at least 5 minutes before accessing internal components. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 129: Figure 66. Repo Operation

    Power is now supplied to the critical load in dual conversion mode from all UPSs. It takes approximately one minute for the UPSs to achieve the dual conversion mode. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 130 Double Conversion mode and supply the critical load. 11. Repeat Steps Step 1 through Step 10 for each UPS in the parallel system. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 131 7 7 . . 4 4 . . 7 7 T T r r a a n n s s f f e e r r f f r r o o m m E E S S S S M M o o d d e e t t o o D D o o u u b b l l e e C C o o n n v v e e r r s s i i o o n n M M o o d d e e To transfer the load to Standard Normal mode: Tap the CONTROLS tab on the main menu navigation bar. The Control screen is displayed. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 132 Tap the MODULES CONTROLS tab on the secondary Control menu navigation bar. The UPM Select screen is displayed. On the UPM Select screen, select the UPM to shutdown. The UPM Control Screen is displayed. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 133 On the UPS being restarted, tap the CONTROLS tab on the main menu navigation bar. The System Control screen is displayed. Tap the GO ONLINE button. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 134: Transfer From Double Conversion To Bypass Mode

    Tap the CONTROLS tab on the main menu navigation bar. The Control screen is displayed. Tap the UPS CONTROLS tab on the secondary navigation bar. The UPS Control screen is displayed. Tap the TURN OFF CHARGER button. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 135: Starting The Parallel System In Double Conversion Mode

    Power is present inside the UPS cabinet until the upstream input feeder circuit breakers and battery breakers are opened. Wait at least 5 minutes before accessing internal components. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 136 Power is present inside the UPS cabinet until the upstream input feeder circuit breakers and battery breakers are opened. Wait at least 5 minutes before accessing internal components. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 137: Figure 67. Optional Minislot Cards

    IRC-MS installation guide. One input can be activated by a switch or dry contact. The voltage source is provided by the card, no external voltage source is needed. For installation and setup of a Minislot card, contact an Eaton service representative. Refer to the manual supplied with the Minislot card for user instructions.
  • Page 138: General Purpose Relay Contact

    It’s also powered by CA Technologies, bringing together the best in hardware and software. PredictPulse Service is included at no charge during the first year of Eaton 93PM UPS operation (warranty period) along with the required connectivity parts. Beyond that, it may be purchased with Eaton Support Agreements or as a standalone subscription after the initial warranty expires.
  • Page 139 Real-time alarm events for all subscribed devices via the PredictPulse mobile app (Apple and Android). You can track all alarms by device. As critical alarms occur, Eaton will acknowledge them so you know when Eaton has diagnosed the alarm (and pending notification of resolution).
  • Page 140 Communication Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 141 The UPS system requires very little preventive maintenance. However, the system should be inspected periodically to verify that the units are operating normally and that the batteries are in good condition. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 142 The foam filters are to be replaced with new or washed filter immediately. The UPS is not meant to be run without filters installed. Close the front door and secure the latch Record maintenance results and any corrective actions in a suitable log. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 143: Figure 68. Air Filter Location

    9 9 . . 2 2 . . 5 5 B B A A T T T T E E R R Y Y M M a a i i n n t t e e n n a a n n c c e e Contact an Eaton service representative for battery maintenance. Battery replacement and maintenance should be performed only by authorized service personnel. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 144: Important Safety Instructions

    Phillips and Pozidriv are registered trademarks of Phillips Screw Company. A basic training course, available from Eaton, gives you a competent working knowledge of the UPS system Copyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
  • Page 145: Specifications

    1 1 0 0 . . 2 2 S S p p e e c c i i f f i i c c a a t t i i o o n n s s The following sections detail the input, output, environmental, and battery specifications for the UPS. Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 146: Product Specifications

    < 2.5° for 100% maximum load imbalance (linear load) Frequency Regulation 0.1 Hz free running Synchronous to Bypass ± 4 Hz (default setting) Frequency Slew Rate 1 Hz per second (default setting) Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 147 Meets IEC 61000-4-2 Level 3 specifications. Withstands up to 4 kV contact pulse without damage and with no disturbance or adverse effect to the critical load. Immunity Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 148 Product Specifications Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 149 For Product installed (and currently located) outside the fifty (50) United States and the District of Columbia, if, in the opinion of Eaton, a Warranted Item is defective, Eaton's sole obligation, at the option of Eaton, will be to refurbish or replace such defective Warranted Item (not including the costs of labor coverage). The defective Warranted Item will be refurbished or replaced onsite at the End-User's location or such other location as determined by Eaton.
  • Page 150 Eaton shall not be responsible for failure to provide service or parts due to causes beyond Eaton's reasonable control. In no case will Eaton's liability under this Warranty exceed the replacement value of the Warranted Items.
  • Page 151 Warranty Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 04...
  • Page 152 16400056604 164000566 04...