6.2.8
System Controls
Tap the CONTROLS tab on the main menu navigation bar to display the Controls screen. Double conversion
operation, transfer to bypass, shutdown, and charger control commands are controlled through this screen. In
addition, the screen displays the current status of the UPS. Figure 6-9 shows the System Control screen.
Table 6-4 describes the control functions and provides instructions to access and use the command menu
screens.
Table 6-5 lists the typical System Status Screen Messages that are displayed during UPS operation.
For UPS operating instructions using the System Controls, see paragraph 6.3.
Figure 6-9. Typical System Control Screen
Table 6-4. Controls Menu Operation
Function
Subfunction
System Controls
System Status
Bypass
Charger
Battery Test
Table 6-5. Typical System Status Messages
Function
UPS
Bypass
Charger
Eaton 93PM UPS (60–100 kW, 480V) Installation and Operation Manual P-164000227—Rev 2
Operation
The CONTROLS tab on the main menu navigation bar displays the System Controls
screen.
GO ONLINE starts the UPS in Double Conversion mode or transfers the UPS to Double
Conversion mode from Bypass mode.
GO TO BYPASS starts the UPS in Bypass mode or transfers the UPS to Bypass mode from
Double Conversion mode.
TURN ON CHARGER/TURN OFF CHARGER sets the battery charger on or off.
RUN BATTERY TEST starts the battery test.
Message
Double Conversion; Bypass; ESS
Off; On; Available
Charger Resting; Charger
UPS Operating Instructions
www.eaton.com/powerquality
6-9