Chapter 9
Product Specifications
9.1
Model Numbers
The UPS is housed in a free-standing cabinet with safety shields behind the door. The UPS is available in
50 or 60 Hz with various output power ratings.
Model
Eaton 93PM-100
Eaton 93PM-100
Eaton 93PM-100
Eaton 93PM-100
Eaton 93PM-100
9.2
Specifications
The following sections detail the input, output, environmental, and battery specifications for the UPS.
9.2.1
UPS Input
Operating Input Voltage
Operating Input Frequency Range
Operating Input Current
Input Current Harmonic Content
Power Factor
Line Surges
Battery Voltage
Battery Charging Capacity
480 Vac wye, 3W + ground. Neutral not used.
50/60 Hz
See Table 3-4.
Reduced for Generator
Adjustable
3% THD at full load
Minimum 0.99
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 8014
432 Vdc
16.5 A maximum per 50 kW module at any load up to100% at nominal input
voltage
Eaton 93PM UPS (60–100 kW, 480V) Installation and Operation Manual P-164000227—Rev 2
Power Rating
60 kW
70 kW
80 kW
90 kW
100 kW
Frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz