UPS Installation Plan and Unpacking
The power wiring terminals are pressure terminations, UL and CSA rated at 90°C. See Table 3-5 for external
power cable terminations.
Figure 4-6 and Figure 4-7 show the location of the UPS power cable terminals.

Table 3-5. UPS External Power Cable Terminations for the Eaton 93PM-100

Terminal Function
AC Input to UPS Rectifier
AC Input to Bypass
AC Output to Critical Load
DC Input from Battery
Customer Ground
NOTE
Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed in Table 3-6.
3-12
Eaton 93PM UPS (60–100 kW, 480V) Installation and Operation Manual P-164000227—Rev 2
Terminal
Function
E1
Phase A
E2
Phase B
E3
Phase C
E6
Phase A
E7
Phase B
E8
Phase C
E9
Phase A
E10
Phase B
E11
Phase C
E4
Battery (+)
E5
Battery (-)
Ground
Ground
Number and Size of Pressure
Termination
AWG or kcmil
2 - #6-250 kcmil
2 - #6-250 kcmil
2 - #6-250 kcmil
2 - #6-250 kcmil
2 - #6-250 kcmil
2 - #6-250 kcmil
2 - #6-250 kcmil
2 - #6-250 kcmil
2 - #6-250 kcmil
4 - #6-250 kcmil
4 - #6-250 kcmil
6 - #14-1/0
www.eaton.com/powerquality
Tightening Torque
Nm (lb in)
Screw Size and Type
22.6 (200)
1/4" Hex
22.6 (200)
1/4" Hex
22.6 (200)
1/4" Hex
22.6 (200)
1/4" Hex
22.6 (200)
1/4" Hex
22.6 (200)
1/4" Hex
22.6 (200)
1/4" Hex
22.6 (200)
1/4" Hex
22.6 (200)
1/4" Hex
22.6 (200)
1/4" Hex
22.6 (200)
1/4" Hex
5.1 (45)
Slotted