Figure 4-9. Battery Shunt Trip and Battery Detect Terminal Detail
Table 4-1. Battery Shunt Trip and Battery Detect Connections and Wire Terminations
Terminal Name
1
48 Vdc Battery Shunt Trip +
2
48 Vdc Battery Shunt Trip –
3
Battery Detect
4
Battery Detect Common
Shunt Trip and
Battery Detect
4
3
2
1
Figure 4-10. Battery Shunt Trip and Battery Detect Terminal Assignments
Eaton 93PM UPS (60–100 kW, 480V) Installation and Operation Manual P-164000227—Rev 2
Description
Output: Contacts used to open battery breaker or disconnect
Input: Contacts used to indicate whether battery breaker is
open or closed.
UPS
Battery Detect Common
Battery Detect
Battery Shunt Trip –
Battery Shunt Trip +
UPS System Installation
Shunt Trip and Battery
Detect Terminals
(See Figure 4-10 for
Terminal Assignments)
Wire Size
Tightening Torque
Twisted Pair Wires
(0.23 Nm)
#1630 AWG
Twisted Pair Wires
#1630 AWG
(0.23 Nm)
www.eaton.com/powerquality
2 lb in
2 lb in
4-13