The UPS ventilation requirements are shown in Table 3-3.

Table 3-3. Air Conditioning or Ventilation Requirements During Full Load Operation

Model
UPS Rating
Eaton 93PM-100
60 kW
Eaton 93PM-100
70 kW
Eaton 93PM-100
80 kW
Eaton 93PM-100
90 kW
Eaton 93PM-100
100 kW
Front

Figure 3-1. UPS Cabinet Dimensions (Front and Right Side Views)

Eaton 93PM UPS (60–100 kW, 480V) Installation and Operation Manual P-164000227—Rev 2
Input/Output Voltage
BTU/hr x1000 (kg-cal/hr)
480/480
480/480
480/480
480/480
480/480
UPS Installation Plan and Unpacking
Heat Rejection
7.16 (1807)
8.36 (2108)
9.12 (2300)
10.26 (2588)
11.40 (2875)
Right Side
Dimensions are in millimeters [inches]
www.eaton.com/powerquality
Minimum Required
Cooling Air Flow
378 liter/sec (800 cfm)