UPS System Installation

Figure 46. REPO Terminal Block Connector Assignments

Normally Closed
REPO Contacts
Table 27. Normally-Open REPO Connections and Wire Terminations
From REPO
Station
Switch Con-
tact Block
(Either
Block)
3 NO
4 NO

Figure 47. Normally-Open REPO Switch Wiring

96
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
UPS REPO
1
EPO_A_B
GND-ISO
UPS
REPO
Termi-
Nam-
Description
nal
e
3
EPO_
Input: Normally-open dry
A
contact used to activate UPS
4
EPO_
EPO from a remote switch
B
REPO
Switch
(NO)
2
3
4
EPO_A
EPO_B
Recommended
Minimum
Wire Size
Twisted Pair Wires
#18 AWG
3
Twisted
Wires
4
Normally Open
REPO Contacts
Size of
Tightening
Wire
Termination
(0.22-0.25 Nm)
#16
#30 AWG
1
2
REPO TB
3
4
Torque
2 lb in