View Data Log
The Data Log provides the administrative user with a listing of all the readings taken by the IPDU-Sx pertaining to the sensors and
IP Devices being monitored. The data log will record the date and time of each reading.
From the Data Log the administrative user can view the logs. In order to clear specific logs, download log entries, or clear the
entire log, use the Web Interface (see page 54). To navigate between pages of logs, pres <Tab> to move between Previous and
Next and press <Enter>.
Log Settings Menus
The Log Settings menus (Figure 124 and Figure 125 ) provide settings for how the IPDU-Sx will react when its Data and Event
logs reach capacity.
Each log can be assigned to a group and any user that receives messages from that group can be notified when capacity is being
reached.
As a capacity overflow action the log can be set to either :
The Data and/or Event log can be set to sent alerts to users via email, syslog, and/or SNMP traps once it has reached 90% of
capacity, allowing them time to react.

Figure 123- Text Menu-View Data Log

Discontinue- stop logging information
Clear and restart- delete all log entries and restart with new entries
Wrap- continue logging but delete the oldest entries and new ones are recorded