Cascaded Installation Via Rs485 Connection; Gsm Modem Connection; Figure 7- Cascade Installation- Rs485 Connection; Figure 8- Connect A Gsm Modem - Network Technologies IPDU-Sx Installation And Operation Manual

Enviromux series secure remote power reboot switch
Table of Contents

Advertisement

NTI Secure Remote Power Reboot Switch

Cascaded Installation via RS485 Connection

Two RJ45 ports are provided on the front of models IPDU-S4 and IPDU-S8. These are used when multiple units are connected
together (cascaded) and controlled as one system using the RS485 Connect method (see page 8). Cascading enables the
monitoring of all sensors and outlets from up to 17 IPDU-S4 or IPDU-S8 (or any combination of each model).
Connect installation, connect a CAT5/5e/6 patch cable with RJ45 male connectors on each end (wired straight thru, pin 1 to pin 1,
pin 2 to pin 2, etc.) between the "Cascade" ports as shown in the image below. The maximum distance from the Master to the last
Slave can be no more than 1000 feet. With this properly connected and configured (pages 38 and 85) , the user can monitor the
sensors and outlets of all systems from either a single connected terminal (page 6) or through the Web Interface.
Cascade
Console
Ethernet
Reset
RJ45-male
connector
The maximum combined length of
cable from the Master unit to the
last Slave unit can be no more than
1000 feet.

GSM Modem Connection

(IPDU-S4 and IPDU-S8 Models only)
If alert notifications via SMS to a cell phone are desired, a GSM modem can be connected to the USB port on the IPDU-S4 / -S8
models. With a GSM modem connected, a user can receive SMS alert messages directly on their cell phone.
modem is powered by the USB port.
A GSM modem that has been tested and is confirmed to be compatible with the IPDU-S4/ -S8 is the iCON 452. To order this
modem, contact NTI and ask for the ENVIROMUX-3GU.
Note: The modem connected to the IPDU-Sx will send SMS messages only. No access to the IPDU-Sx is possible
through the modem.
IPDU-S8 MASTER with RS485 Slaves (FRONT VIEW)
RJ45 Sensors
Sensor
Fault
Power
IP
Trip
Fault

Figure 7- Cascade installation- RS485 Connection

Figure 8- Connect a GSM modem

Total Outlet
Current
RJ45-male
connector
IPDU-S8 RS485 SLAVE (FRONT VIEW)
Total Outlet
Current
Cascade
Console
RJ45 Sensors
Ethernet
Sensor
Fault
Power
Reset
IP
Trip
Fault
IPDU-S8 RS485 SLAVE (FRONT VIEW)
Total Outlet
Current
RJ45 Sensors
Cascade
Console
Ethernet
Sensor
Fault
Power
Reset
IP
Trip
Fault
UP TO 16 UNITS CONNECTED
IPDU-S8 RS485 SLAVE (FRONT VIEW)
Total Outlet
Current
RJ45 Sensors
Cascade
Console
Ethernet
Sensor
Fault
Power
Reset
IP
Trip
Fault
8
For an RS485
NTI
R
R
ENVIROMUX
Netw ork Technolog ies Inc
NTI
R
R
ENVIROMUX
Ne t wo rk T e chn o lo gie s In c
NTI
R
ENVIROMUX
R
Ne t wo rk T e chn o lo gie s In c
NTI
R
ENVIROMUX
R
Ne t wo rk T e chn o lo gie s In c
The external GSM