Figure 88-Text Menu-Ip Device Settings - Network Technologies IPDU-Sx Installation And Operation Manual

Enviromux series secure remote power reboot switch
Table of Contents

Advertisement

NTI Secure Remote Power Reboot Switch
From the IP Device Settings menu, the user can enter the name and address of the IP Device, assign a sensor group, and define
how the IP Device will be monitored.
IP Device Settings
Description
Description
The description of the IP Device that will be viewed in the Summary page and in the body of alert
messages
Group
Assign the IP device to either group 1 or 2
IP Address
The IP address of the IP Device
Ping Period
Enter the frequency in minutes or seconds that the IPDU-SX should ping the IP Device
Timeout
Enter the length of time in seconds to wait for a response to a ping before considering the attempt a
failure
Retries
Enter the number of times the IPDU-SX should ping a non-responsive IP device before changing its
status from normal to alarm and sending an alert
Press <Tab> to highlight Save and press <Enter> to save before pressing <Esc> to exit.
From the Alert Settings menu, the user can enable/disable alert messages to be sent when the IP Device is in an alert state and
configure when and how alert messages are sent.
described on page 69.
Under Power Outlet Association, if the IP device is connected to one of the power outlets on the IPDU-
Sx, the IPDU-Sx can automatically cycle the power to the chosen outlet when the IP device is determined to be in a state of alarm.
The power cycle characteristics will be those configured under the power outlet configuration under "Power Outlet Operation
Settings" (page 66).

Figure 88-Text Menu-IP Device Settings

The alert settings and data logging are the same as for sensor configuration,
74

Advertisement

Table of Contents
loading

This manual is also suitable for:

Enviromux ipdu-sx

Table of Contents