NTI Secure Remote Power Reboot Switch
Power Outlet Settings
Description
Group
Notification Settings
Disable Notifications
Enable Syslog Notifications
Enable SNMP traps
Enable Email Notifications
Email Subject
Enable SMS Alerts
(IPDU-S4 / -S8 only)
Outlet Operation Settings
Operation Mode
Manual Operation Changes
Mode
Cycle Duration
Periodic Cycle Duration
Periodic Type
Periodic Hour
Periodic Minute
Periodic Day
Periodic Month
Periodic Year
Default outlet value
Multiple Event Preferred Value
Note: Alerts are also indicated by illuminated LEDs on the front of the IPDU-Sx (page 7).
More about Groups
Groups are used to create a common relationship between sensors, IP devices, power outlets, etc. and their alert messages. All
items being monitored are assigned to either group 1 or group 2. All users (a maximum number of 16 including the root user) can
either receive alert messages from items in group 1, group 2, both groups, or neither.
Be sure to press the Save button to save the configuration settings.
More about Operation Modes
In Manual Mode, the outlet will only power cycle when it is performed through the Power Outlet Status page or through the text
menu.
In Periodic Mode, the outlet will power cycle based on the settings configured as described in the table above.
In Associated Mode, the outlet can be controlled based on the alert status of a sensor or IP address. When configured to do so
(page 24), the outlet can be powered ON or OFF when a sensor is in alert mode, and/or when it returns to normal state, or power
cycled when an IP Device is in alert mode.
Note: An outlet configured for Associated or Periodic operating mode can be manually powered ON/OFF. If "Manual
Operation Changes Mode" (above) is checked, manually changing the ON/OFF state of an outlet configured for
Associated Mode or Periodic Mode will change the operating mode to Manual Mode until the outlet is reconfigured.
Description
The description of the outlet that will be viewed in the Summary page and in the body of alert
messages
Assign the outlet to either group 1 or 2
Place a checkmark in the box to prevent notifications from being sent when this outlet's status
changes
Place a checkmark in this box to have alert notifications sent via Syslog messages
Place a checkmark in this box to have alert notifications sent via SNMP traps (v2c)
Place a checkmark in this box to have alert notifications sent via Email
Enter the subject to be viewed when an email alert message is received
Place a checkmark in this box to have alert notifications sent via SMS message (requires
modem)
Choose between Manual, Periodic, or Associated operating modes for the outlet
Place a checkmark here if you want the operating mode to be forced into Manual mode if you
manually override the outlet status from the Power Outlet Status page (page 16)
Time period (1-300 seconds) the outlet will remain OFF during a manual power cycle or an
associated power cycle
Time period in minutes or hours the outlet will remain OFF during a periodic power cycle
If the operation mode is set to periodic, choose the type of periodic schedule between one time,
daily, weekly, monthly, or none
Choose which hour of the day for the periodic cycle to occur (00-23)
Choose the minute within the hour of the day for the periodic cycle to occur (00-59)
Choose the day for the periodic cycle to occur (for one-time and monthly settings, enter a value
between 1-31; for weekly setting, enter a value 1-7, Sun = 1, Mon=2 .....Sat = 7)
Choose which month of the year for the periodic cycle to occur. This only applies when the
Periodic Type is set to "one time".
Enter the year for the periodic cycle to occur. This only applies when the Periodic Type is set to
"one time".
Choose the state of the outlet at power-On of the IPDU- Outlet ON or Off
Choose the preferred outlet state when more than one event can control the outlet
(if one event is configured to turn the outlet OFF, and another event to turn the outlet ON, this
setting will decide the state of the outlet)
19