Specifications

Ratings and Characteristics
S8AS-24006@
Item
Model
Efficiency (Typ.)
Input
Voltage range (See note 1.)
condi-
Frequency (See note 1.)
tions
Current
100-V input
200-V input
Power factor
Harmonic current
Leakage cur-
100-V input
rent
200-V input
Inrush current
100-V input
(See note 2.)
200-V input
Output
Number of branches
condi-
Maximum cutoff output current
tions
(per branch)
Total output current
Allowable voltage range (See
note 3.)
Ripple noise voltage
Output leakage current
Input fluctuation
Load fluctuation (rated input
voltage)
Temperature fluctuation
Startup time (See note 2.)
Output hold time (See note 2.)
Func-
Tripping func-
Abnormal volt-
tions
tions
age tripping
Abnormal cur-
rent tripping
(See note 2.)
Abnormal total
current tripping
Tripping Alarm
Output
Undervolt-
Undervoltage
age detec-
detection
tion functions
Undervoltage
detection out-
put
Maintenance
Maintenance
forecast mon-
forecast moni-
itor function
tor
Maintenance
forecast moni-
tor output
22
S8AS-24006
80% min.
100 to 240 VAC (85 to 264 VAC)
50/60 Hz (47 to 63 Hz)
3.8 A max.
2.0 A max.
0.95 min.
EN61000-3-2
0.5 mA max.
1.0 mA max.
25 A max. (for a cold start at 25°C)
50 A max. (for a cold start at 25°C)
6
3.8 A
10 A
±10 A (with V.ADJ)
2.0%[P-P] max. (for rated input and output voltage) (See note 4.)
10 mA max.
0.5 % max. (Input: 85 to 264 VAC, 100 % load) (See note 5.)
4.0 % max. (rated input, 0% to 100% load) (See note 5.)
0.05%/°C max.
3,000 ms max. (for rated input and output voltage) (See note 4.)
20 ms min. (for rated input and output voltage) (See note 4.)
28.8 V (Cannot be changed.)
Setting range: 0.5 to
3.8 A (in 0.1-A incre-
ments)
Branch outputs are cut off when the total output current is more than 17 A for
2 s, 15 A for 5 s, 13 A for 10 s, or 12 A for 20 s.
Photoswitch output
30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual volt-
age: 2 V max.
Setting range: 18.0 to
26.4 V (in 0.1-V incre-
ments)
Photoswitch output
30 VDC max. and 50 mA max., Leakage current: 0.1 mA max.,
Residual voltage: 2 V max.
Setting range: 0.0 to
5.0 yr (in 0.5-yr incre-
ments)
Photoswitch output
30 VDC max. and 50 mA max., Leakage current: 0.1 mA max.,
Residual voltage: 2 V max.
S8AS-24006N
3.8 A (Cannot be
changed.)
20.0 V (Cannot be
changed.)
0.5 yr (Cannot be
changed.)
Section 2-3
S8AS-24006R
Setting range: 0.5 to
3.8 A (in 0.1-A incre-
ments)
Setting range: 18.0 to
26.4 V (in 0.1-V incre-
ments)
Setting range: 0.0 to
5.0 yr (in 0.5-yr incre-
ments)

Hide quick links: