Omron S8AS User Manual page 87

Smart power supply
Table of Contents

Advertisement

Special Settings and Communications Settings
Tripping Input Type: TGS (Trigger Sense)
t g s
Switch to the
Communica-
tions Unit No.
Setting (UNO)
for models
with communi-
cations. (See
note.)
Note: For mod-
els without com-
munications,
switch to Reset
Method Setting
(page 76).
(4) Once the TRG input goes OFF, the cut-off branch outputs can be recon-
nected by pressing the Reset Key.
(5) When all outputs are cut off simultaneously in Test mode or the shutdown
sequence operation is executed via communications, the branch outputs
will be cut off regardless of the external tripping input trigger setting.
The Tripping Input Condition Setting (TGS) will be displayed if the Up (SEL)
Key (
) is pressed from the External Tripping Input Trigger Setting Display
(TRG).
This parameter sets the tripping input type for each branch output that has
tripping input (TRG) enabled.
e g e
l V l
(Returns to TGS display.)
Press the
Key to display the tripping input type.
The setting can be changed by pressing the
EGE (Edge): Output is cut off when TRG input changes
from OFF to ON.
LVL (Level): Output is cut off when TRG input changes from
OFF to ON, and is connected when TRG
input changes from ON to OFF.
Change the setting with the
• The S8AS will automatically return to the TGS display if
no key is pressed within 3 s.
When the
Key is pressed, the SV display will flash.
When the flashing stops, the new setting will be saved and
the S8AS will return to TGS display.
• If you want to confirm the new setting, press the
again from the TGS display.
Section 4-7
or
Key.
or
Key.
Key
69

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents