Omron S8AS User Manual page 113

Smart power supply
Table of Contents

Advertisement

Frame Structure
Addresses
Monitored Values
Alarm Status
Do not operate or access branch outputs that do not exist in corresponding
S8AS model.
Variable Type 80
Address
0000
Present input voltage (V)
0001
Total current (A)
0002
Run time (kh)
0003
Internal temperature (°C)
0004
Remaining life (years)
Address
0010
Present current, branch output 1
0011
Present current, branch output 2
0012
Present current, branch output 3
0013
Present current, branch output 4
0014
Present current, branch output 5
0015
Present current, branch output 6
0016
Present current, branch output 7
0017
Present current, branch output 8
0020
Peak output current, branch output 1
0021
Peak output current, branch output 2
0022
Peak output current, branch output 3
0023
Peak output current, branch output 4
0024
Peak output current, branch output 5
0025
Peak output current, branch output 6
0026
Peak output current, branch output 7
0027
Peak output current, branch output 8
Note
If the upper limit of the displayable range is exceeded, the upper limit will be
displayed. If the lower limit is exceeded, the lower limit will be displayed.
The alarm status is used to read the controller status.
Name
00A3 to 012C (16.3 to 30.0 V)
If the lower limit is exceeded:
0000
If the upper limit is exceeded:
7FFF
0000 to 0190 (0.0 to 40.0 A)
If the upper limit is exceeded:
7FFF
0000 to 03E7 (0 to 999 kh)
1-kh increments
FFEC to 0064 (−20 to 100°C)
If lower limit is exceeded:
8000
If upper limit is exceeded:
7FFF
0000 to 0096 (0.0 to 15.0
years)
Name
0000 to 00C8 (0.0 to 20.0 A)
Section 6-2
Data range
Data range
95