Table of Basic Functions
Setting Functions
10
Monitored
parameter
Branch output
Displays individual branch
peak current
output peak currents.
Replacement
Displays the estimated num-
time
ber of years left until the
S8AS needs to be replaced.
(Setting: 0.0 to 5.0 years, in
0.5-year increments.)
Internal tempera-
Displays the S8AS's inter-
ture
nal temperature.
Refer to SECTION 4 Parameter Settings for details on parameter settings.
(These parameters cannot be changed for the S8AS-24006N/48008N.)
Data name
Undervoltage
The undervoltage detection output (LOW) is output
detection thresh-
when the output voltage of the S8AS falls below this
old
detection threshold. The detection threshold can be
set in 0.1-V increments. Branch outputs will not be
cut off.
Abnormal current
The current tripping threshold can be set for each
tripping threshold
branch output in 0.1-A increments.
Abnormal current
The tripping type can be set for each branch output.
tripping type
USU: Standard (tripping within 100 ms)
INS: Instantaneous (tripping within 20 ms)
LNG: Extended (tripping within 1,000 ms)
Maintenance
Set the expected number of years until the S8AS
forecast monitor
needs to be replaced. When the estimated value falls
function
below the set value, the maintenance forecast moni-
tor output (LFE) will turn ON. (The photoswitch output
will turn OFF.)
Over-tempera-
An excessive temperature rise inside the S8AS will
ture threshold
be detected and the over-temperature output (TMP)
will turn ON. (The photoswitch output will turn OFF.)
This output can be used to control cooling equipment
to reduce the temperature in the control panel.
Startup
The connection of branch outputs may be initiated by
sequence
communications or when the power is turned ON,
and a time delay can be set for the connection
sequence. Connecting the branch outputs in
sequence instead of simultaneously can reduce the
inrush current and reduce the load on the Power Sup-
ply.
Shutdown
Branch outputs can be disconnected in sequence ini-
sequence
tiated by communications or an external tripping input
(TRP), and a time delay can be set for the sequence.
Tripping trigger
The external tripping input function (TRG) can be
input
enabled (ON) or disabled (OFF) for each branch out-
put.
Tripping trigger
The tripping trigger type can be set for all branches
type
that have the tripping input function enabled.
Details
Seven-
segment
display
0.0 to 20.0 Lit
FUL, HLF
0.0 to 5.0
−20 to 100 Not lit
Detail
Section 1-3
Indications
Branch
Unit
output
indicators
number
indicators
A
(flashing)
Not lit
Yrs
°C
Setting
range
18.0 to
26.4 V
0.5 to
3.8 A
USU/INS/
LNG
0.0 to
5.0 yr
25 to 90°C
0.0 to
99.9 s
0.0 to
99.9 s
OFF, ON