Individual Branch Output Settings
Setting the Abnormal Current Tripping Type: C-T (Cutoff Type)
Switch to the
Undervolt-
age Detec-
tion Output
setting (V-U).
62
This parameter can be set in protection level 0 only.
Select the current tripping type for the displayed branch output number.
(The branch output that was most recently modified will be the current branch
output regardless of the operating mode.)
c -
t
(To change the
branch output)
u s u
i n s
l n g
(Returns to C-T display.)
Press the
Key to display the setting.
USU (Standard):
USU is an abbreviation of "usually."
The output will be cut off within 100 ms.
INS (Instantaneous):
INS is an abbreviation of "instantaneous."
The output will be cut off within 20 ms.
LGN (Extended detection):
LNG is an abbreviation of "long."
The output will be cut off within 1,000 ms.
The setting can be changed by pressing the
The S8AS will automatically return to the C-T display if no
key is pressed within 3 s.
The setting can be changed by pressing the
When the
Key is pressed, the SV display will flash.
When the flashing stops, the new SV will be saved and the
S8AS will return to C-T display.
If you want to confirm the new setting, press the
again from the C-T display.