S8FS-G

Specifications

Item
Efficiency *
Voltage range *
Frequency *
Current *
Power factor
Input
Leakage current *
Inrush current *
(for a cold start at
25°C)
Rated Output Current
Voltage adjustment range *
Ripple & Noise
voltage *
Input variation influence *
Load variation influence *
Output
Temperature
variation influence
Startup time *
Hold time *
Overload protection
Overvoltage protection *
Overheat protection
Additional
Series operation
functions
Parallel operation
Remote sensing
Remote control
Output indicator
Withstand voltage
Insulation
Insulation resistance
Ambient operating temperature
Storage temperature
Environment
Ambient operating humidity
Vibration resistance
Shock resistance
MTBF
Reliability
Life expectancy *
Dimensions (W×H×D)
Weight
Construction
Cooling fan
Degree of protection
Harmonic current emissions
EMI *
EMS
Standards
Safety Standards
Marine Standards
SEMI
* Refer to Ratings, Characteristics, and Functions on page 11.
4
Power rating
Output voltage
5 V
80% typ.
100 VAC input
80% typ.
200 VAC input
80% typ.
230 VAC input
Single phase, 85 to 264 VAC, 120 to 370 VDC
50/60 Hz (47 to 450 Hz)
0.32 A typ.
100 VAC input
0.2 A typ.
200 VAC input
---
0.5 mA max.
100 VAC input
1 mA max.
200 VAC input
14 A typ.
100 VAC input
28 A typ.
200 VAC input
3 A
−10% to 15% (with V.ADJ)
100 to 240 VAC input
40 mVp-p max.
0.5% max.
1.0% max.
100 to 240 VAC input
0.05%/°C max.
1,000 ms max.
100 VAC input
1,000 ms max.
200 VAC input
15 ms typ.
100 VAC input
75 ms typ.
200 VAC input
Yes, automatic reset
Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on
the input again)
No
Yes (For up to two Power Supplies, external diodes are required.)
No (However, backup operation is possible, external diodes are required.)
No
No
Yes (LED: Green)
3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA
2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA
1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA
100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC
−20 to 70°C (Derating is required according to the temperature.) (with no condensation or icing)
−25 to 75°C (with no condensation or icing)
90% max. (Storage humidity: 90% max.)
10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions
150 m/s
2
, 3 times each in ±X, ±Y, ±Z directions
135,000 hrs min.
10 years min.
Refer to Dimensions on page 18.
250 g
No
---
Conforms to EN 61000-3-2
Conforms to EN 61204-3 Class B, EN 55011 Class B
Conducted Emissions
Radiated Emissions Conforms to EN 61204-3 Class B, EN 55011 Class B
Conforms to EN 61204-3 high severity levels
UL 508 (Listing, excluding models with connector option)
UL 60950-1 (Recognition, OVCII [≤ 3,000 m], Pol2)
CSA C22.2 No.107.1 (excluding models with connector option)
CSA C22.2 No.60950-1 (excluding models with connector option)
EN 50178 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2)
EN 60950-1 (OVCII [≤ 3,000 m], Pol2)
Conforms to EN/IEC 61558-2-16.
No
Conforms to F47-0706 (200 VAC input)
15 W
12 V
15 V
84% typ.
84% typ.
84% typ.
84% typ.
84% typ.
84% typ.
1.3 A
1 A
40 mVp-p max.
40 mVp-p max.
14 ms typ.
15 ms typ.
70 ms typ.
75 ms typ.
24 V
85% typ.
86% typ.
86% typ.
0.65 A
60 mVp-p max.
15 ms typ.
70 ms typ.

Hide quick links: